beautypg.com

ERICO ROD LOCK Plywood Pre-set Anchor User Manual

Caddy® rod lock plywood pre-set anchor

background image

Notes:

1. Allowable tension & shear load capacities are calculated using an applied safety factor of 3.0

2. Allowable working load must be the lesser of product allowable tension & shear loads showing above table.

3. NFPA® 13 design requirements are 5 times the weight of the water filled pipe plus 250 lbs.

4. MSS requires the safety factor of 3.5

5. Allowable loads for anchors to resist short term loads such as earthquake or wind may be increased by 33.33% for the duration of the

load where permitted by code.

* Do not use a hot dip galvanized threaded rod.

* For in-door applications only.

Part Number

Article Number

Rod Size

Max. FM® 1951 pipe size

CRLW37EG

N/A

3/8"

4" or DN100

CRLWM10EG

390019

M10

CRLW50EG

N/A

1/2"

8" or DN200

CRLWM12EG

390020

M12

Allowable Tension & Shear Loads for Threaded Rod*

Threaded rod itself

Steel Type

ASTM®/ISO® Steel

designation

Threaded rod size

Minimum Yield

strength

Minimum Tensile

strength

Allowable Tension

Load

Lbs [kN]

Allowable Shear

Load

Lbs [kN]

Standard Carbon

Steel Rod

A307, Grade C

3/8"

36.0 ksi

58.0 ksi

2,115 [9.5]

1,090 [4.9]

1/2"

3,755 [16.9]

1,940 [8.7]

A36

3/8"

36.0 ksi

58.0 ksi

2,115 [9.5]

1,090 [4.9]

1/2"

3,755 [16.9]

1,940 [8.7]

High Strength

Carbon Steel Rod

A193, Grade B7

3/8"

105.0 ksi

120.0 ksi

4,375 [19.7]

2,255 [10.1]

1/2"

7,775 [35.0]

4,050 [18.2]

Stainless Steel Rod

(SS304/ SS316)

A193, Grade

B8/B8M, Class 1

3/8"

30.0 ksi

75.0 ksi

2,720 [12.1]

1,400 [6.2]

1/2"

4,850 [21.6]

2,500 [11.1]

Europe Steel Rod

ISO 898-1,

Class 4.6

M10

240 MPa

400 MPa

2,350 [10.5]

1,210 [5.4]

M12

3,390 [15.1]

1,745 [7.8]

Product Allowable Tension & Shear Loads with Normal-Weight Concrete (See Notes 1, 2, 3, 4 & 5)

Normal-Weight Concrete having 3,000 psi [20.7 Mpa] minimum compression strength

Threaded Rod Steel

Type

Threaded

rod size

Minimum

Concrete slab

Thickness

Inch [mm]

Minimum Edge

Distance Inch

[mm]

Minimum

Spacing

Inch [mm]

Ultimate

Tension Load

Lbs [kN]

Ultimate

Shear Load

Lbs [kN]

Allowable

Tension Load

Lbs [kN]

Allowable

Shear Load

Lbs [kN]

A307, Grade C

3/8"

3-1/4" [83mm]

6" [152mm]

8" [203mm]

4,220 [18.8]

3,270 [14.6]

1,407 [6.3]

1,090 [4.9]

1/2"

4,820 [21.7]

5,820 [25.9]

1,605 [7.2]

1,940[8.7]

A36

3/8"

4,220 [18.8]

3,270 [14.6]

1,407 [6.3]

1,090 [4.9]

1/2"

4,820 [21.7]

5,820 [25.9]

1,605 [7.2]

1,940[8.7]

A193, Grade B7

3/8"

4,220 [18.8]

5,330 [24.0]

1,407 [6.3]

1,775 [8.0]

1/2"

4,820 [21.7]

7,400 [33.3]

1,605 [7.2]

2,465 [11.1]

A193, Grade

B8/B8M, Class 1

(SS304/ SS316)

3/8"

4,220 [18.8]

4,210 [18.7]

1,407 [6.3]

1,405 [6.2]

1/2"

4,820 [21.7]

7,400 [33.3]

1,605 [7.2]

2,465 [11.1]

Europe ISO Class 4.6

M10

4,220 [18.8]

3,630 [16.2]

1,407 [6.3]

1,210 [5.4]

M12

4,820 [21.7]

5,235 [23.3]

1,605 [7.2]

1,745 [7.8]

TECHNICAL SUPPORT:

www.erico.com

CFS479_C

INSTRUCTION SHEET

1 OF 2

© 2013, 2014 ERICO International

Corporation.

CADDY® ROD LOCK Plywood Pre-set Anchor

3/8 inch, 1/2 inch, M10 and M12

WARNING:

ERICO products shall be installed and used only as indicated in ERICO product instruction sheets and training materials. Instruction sheets are available at

1.

www.erico.com and from your ERICO customer service representative.

ERICO products must never be used for a purpose other than the purpose for which they were designed or in a manner that exceeds specified load ratings.

2.

All instructions must be completely followed to ensure proper and safe installation and performance.

3.

Improper installation, misuse, misapplication or other failure to completely follow ERICO's instructions and warnings may cause product malfunction, property

4.

damage, serious bodily injury and death.

Products that are manufactured using spring steel components shall be used only in a non-corrosive indoor environment.

5.

All pipe supports, hangers, intermediate components and structural attachments must ONLY be used as described herein and are NEVER to be used for any

6.

other purpose.

NOTE: All load ratings are for static conditions and do not account for dynamic loading such as wind, water or seismic loads, unless otherwise noted.
The customer is responsible for:

a. Conformance to all governing codes.

b. The integrity of structures to which the products are attached, including their capability of safely accepting the loads imposed, as evaluated by a qualified

engineer.

c. Using appropriate industry standard hardware as noted above.
SAFETY INSTRUCTIONS:

All governing codes and regulations and those required by the job site must be observed.

Always use appropriate safety equipment such as eye protection, hard hat, and gloves as appropriate to the application.
ASTM is a registered trademark of American Society for Testing and Materials

FM is a registered certification mark of FM Approvals LLC, LTD

ISO is a registered trademark of International Organization for Standardization

NFPA is a registered trademark of National Fire Protection Association, Inc.

CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH, and LENTON are registered trademarks of ERICO International Corporation.