ERICO Branch Line Restraint, Structural Attachment Fitting for Concrete or Wood User Manual
ERICO Accessories for electrical
Used for
concrete
or wood.
Powers Fastener
part number 2722sd.
For more information
go to www.powers.com
3/8"-16
side
1/2"-13
side
4. Rotate barrel to 3/8"-16 side or 1/2"-13 side, based
on threaded rod needed for application
1. Orient part in direction needed for installation.
2. For concrete, pre-drill using 3/16" taper bit drill at least
2-1/4" deep. Clear the hole of dust and other material.
For installation in wood start at step 3.
3. Use standard screw gun with a depth sensitive nose
piece or clutch for correct seating of fastener. Use a
size 5/16"[8mm] hex head socket or flat head screwdriver.
Drive the anchor in a continuous motion until fastener is
fully seated.
Branch Line Restraints are intended to be installed in accordance with NFPA®-13 and manufacturer's
installation instructions.
NA Part
Number
EU Article
Number
Rod Size
UL® Load Rating
FM® Load Rating
45°-59°
60°-74°
75°-90°
CSBBRS2EG
---
3/8", 1/2"
425lbs (1891N)
290 lbs (1290N)
200lbs (890N)
210lbs (935N)
CSBBRS2MEG
402240
M10, M12
CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH, and LENTON are registered trademarks of ERICO International Corporation.
TECHNICAL SUPPORT:
www.erico.com
CFS448_D
INSTRUCTION SHEET
The customer is responsible for:
a. Conformance to all governing codes.
b. The integrity of structures to which the products are attached, including their capability of safely accepting the loads imposed, as evaluated by a qualified engineer.
c. Using appropriate industry standard hardware as noted above.
SAFETY INSTRUCTIONS:
All governing codes and regulations and those required by the job site must be observed.
Always use appropriate safety equipment such as eye protection, hard hat, and gloves as appropriate to the application.
1 OF 2
© 2011, 2012 ERICO International Corporation
WARNING:
ERICO products shall be installed and used only as indicated in ERICO product instruction sheets and training materials. Instruction sheets are available at
1.
www.erico.com and from your ERICO customer service representative.
ERICO products must never be used for a purpose other than the purpose for which they were designed or in a manner that exceeds specified load ratings.
2.
All instructions must be completely followed to ensure proper and safe installation and performance.
3.
Improper installation, misuse, misapplication or other failure to completely follow ERICO's instructions and warnings may cause product malfunction, property
4.
damage, serious bodily injury and death.
Products that are manufactured using spring steel components shall be used only in a non-corrosive indoor environment.
5.
All pipe supports, hangers, intermediate components and structural attachments must ONLY be used as described herein and are NEVER to be used for any
6.
other purpose.
FM is a registered certification mark of FM Approvals LLC, LTD
NFPA is a registered trademark of National Fire Protection Association, Inc.
UL is a registered trademark of UL LLC