Installation:
- Insert pipe
- Close pipe clamp by pressing

the clamp part upward
- Let screw head lock

in the tabs
- Use a screwdriver to

tighten the two screws
- Tighten pipe clamp

until tabs are parallel

UL listed for use with CPVC pipe as a

hanger and surge restraint

4.52 Nm

40 inch-lbs

Bottom Beam Installation

Finish:

Electro-galvanized Zinc

=Not UL Listed

*

*

Top Beam Installation

!

=FM Approved

!

!

!

!

!

!

!
!

!

!

*

*

**

*

To comply with UL203 Listing in the top beam installation the hex

nut of the pipe hanger must be inserted onto a threaded rod and

rest directly on the structural member.

®

®

CPVC Non-Insulated Pipe Clamp

3/8

Threaded Rod

Part Number

M10

Threaded Rod

Part Number

M12

Threaded Rod

Part Number

Nominal

Pipe Size

Inches

Outside Dia.

Of Pipe

(Inches) / mm

4290050EG

595052

1/2

(0.84) / 21.3

4290075EG

595053

3/4

(1.05) / 26.7

4290100EG

595054

1

(1.32) / 33.4

4290125EG

595056

1-1/4

(1.67) / 42.2

4290150EG

595057

1-1/2

(1.90) / 48.3

4290200EG

595059

2

(2.37) / 60.3

4290250EG

595061

596060

2-1/2

(2.87) / 73

4290300EG

595062

596062

3

(3.50) / 88.9

4290350EG

3-1/2

(4.00) / 101.6

4290400EG

595063

596063

4

(4.50) / 114.3

4290500EG

595066

5

(5.56) / 141.3

INSTRUCTION SHEET





All rights reserved. CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH, and LENTON are registered trademarks of ERICO International Corporation.

TECHNICAL SUPPORT:

www.erico.com

CFS397_H

INSTRUCTION SHEET

NOTE: All load ratings are for static conditions and do not account for dynamic loading such as wind, water or seismic loads, unless otherwise noted.
The customer is responsible for:

a. Conformance to all governing codes.

b. The integrity of structures to which the products are attached, including their capability of safely accepting the loads imposed, as evaluated by a qualified engineer.

c. Using appropriate industry standard hardware as noted above.

SAFETY INSTRUCTIONS:

All governing codes and regulations and those required by the job site must be observed.

Always use appropriate safety equipment such as eye protection, hard hat, and gloves as appropriate to the application.

1 OF 1

© 2009, 2010, 2011 ERICO International Corporation

WARNING:

ERICO products shall be installed and used only as indicated in ERICO product instruction sheets and training materials. Instruction sheets are available at

1.

www.erico.com and from your ERICO customer service representative.

ERICO products must never be used for a purpose other than the purpose for which they were designed or in a manner that exceeds specified load ratings.

2.

All instructions must be completely followed to ensure proper and safe installation and performance.

3.

Improper installation, misuse, misapplication or other failure to completely follow ERICO's instructions and warnings may cause product malfunction, property

4.

damage, serious bodily injury and death.

Products that are manufactured using spring steel components shall be used only in a non-corrosive indoor environment.

5.

All pipe supports, hangers, intermediate components and structural attachments must ONLY be used as described herein and are NEVER to be used for any

6.

other purpose.

®

FM is a registered certification mark of FM Approvals LLC, LTD

UL is a registered trademark of Underwriters Laboratories, Inc.