p/n: 029-0021-68-0
8.6
FLOW SENSORS
Each Hale foam system requires a flow sensor to operate. Pipe size must be selected based on
the minimum and maximum water flow in the foam capable discharge. Following is a list of pipe
size and rated flow ranges along with flow sensor saddle clamp part numbers. In all instances a
weld fitting may be substituted for the saddle clamp.
Pipe Size
Flow Range
GPM
LPM
1½” (38mm)
10 - 330
38 - 1,249
2” (50mm)
20 - 550
76 - 2,082
2½” (64mm)
30 - 800
114 - 3,028
3” (76mm)
50 - 1,250
189 - 4,732
4” (102mm)
75 - 1,800
284 - 6,814
SCV or DCV
30 - 750
114 - 2,839