Hale FoamLogix Water and Foam Calibrate User Manual
Quick start guide, Foamlogix water & foam direct calibration), Direct calibration
Quick Start Guide
(FoamLogix Water & Foam Direct Calibration)
Note: If foam and water calibration factors are not know,
use the separate foam and water flow calibration instruction
sheets provided, Class1 p/n: 113968 and 113966.
1.
Press and hold the DISPLAY button
(
i
) on the FoamLogix display until
PASS is shown.
2.
Continue to hold the DISPLAY (
i
)
button while pressing the DECREASE
and INCREASE buttons in this order:
DECREASE, INCREASE, DE-
CREASE, INCREASE ( ).
A d appears with each press of the
DECREASE button; a u appears with
each press of the INCREASE button.
3.
Release the DISPLAY button (
i
).
The display shows the FOAM FLOW
calibration factor with the first digit
flashing. (See Figure 3.) Enter the
new calibration factor by pressing the
INCREASE or DECREASE buttons
( or ) to change the value of the
flashing digit.
4.
Press the red ON/OFF button ( ) to
select the next digit – it begins flashing.
(See Figure 3a.)
5.
Press the DISPLAY button (
i
) to cali-
brate the water flow calibration factor
.
Direct
Calibration
DDDDD
DDDDD
DDDDD
DDDDD
DDDDD
DDDDD
Figure
3
Figure
3a
Figure
2
Figure
1
THIS QUICK START GUIDE IS ONLY INTENDED AS A BRIEF OVERVIEW TO THE
OPERATION OF THE FOAMLOGIX 2.1A, 3.3 AND 5.0 SYSTEMS AND IS NOT
INTENDED TO BE A REPLACEMENT FOR THE INSTALLATION / OPERATION
MANUAL (HALE P/N: 029-0020-74-0 OR 029-0020-68-0) PROVIDED WITH EACH
SYSTEM. ALSO AVAILABLE ON-LINE – WWW.CLASS1.COM.