Hale FoamLogix Water and Foam Calibrate User Manual

Quick start guide, Foamlogix water & foam direct calibration), Direct calibration

background image

Quick Start Guide

(FoamLogix Water & Foam Direct Calibration)

Note: If foam and water calibration factors are not know,
use the separate foam and water flow calibration instruction
sheets provided, Class1 p/n: 113968 and 113966.

1.

Press and hold the DISPLAY button
(

i

) on the FoamLogix display until

PASS is shown.

2.

Continue to hold the DISPLAY (

i

)

button while pressing the DECREASE
and INCREASE buttons in this order:
DECREASE, INCREASE, DE-
CREASE, INCREASE ( ).

A d appears with each press of the
DECREASE button; a u appears with
each press of the INCREASE button.

3.

Release the DISPLAY button (

i

).

The display shows the FOAM FLOW
calibration factor with the first digit
flashing. (See Figure 3.) Enter the
new calibration factor by pressing the
INCREASE or DECREASE buttons
( or ) to change the value of the
flashing digit.

4.

Press the red ON/OFF button ( ) to
select the next digit – it begins flashing.
(See Figure 3a.)

5.

Press the DISPLAY button (

i

) to cali-

brate the water flow calibration factor

.

Direct

Calibration

DDDDD

DDDDD

DDDDD

DDDDD

DDDDD

DDDDD

Figure

3

Figure

3a

Figure

2

Figure

1