How to Connect an EPO Switch to the ATS

InfraStruXure Power Generation System

65

3. Test the EPO switch to ensure it is wired properly and working correctly:

a. Place the Arm/Test rocker switch on the ATS monitoring unit in the Test position. The EPO

state LEDs should be off and the ATS display interface should show the following alarm (in

addition to any other active alarms):

b. Engage the EPO switch (if your switch is momentary, engage while one person is watching

the EPO state LEDs and another is at the EPO switch).

c. Observe the EPO LEDs. If the switch is wired properly and working correctly, both of the

EPO state LEDs should light red when the switch is engaged.

d. If the test was successful, return the Arm/Test rocker switch to the Arm position. The ATS

display interface will clear the EPO test mode alarm. If the test was not successful, refer to

the following troubleshooting chart:

e. Repeat this test for each EPO switch installed.

4. After testing is completed, ensure the Arm/Test rocker switch is in the Arm position on the

ATS monitoring unit.

Problem

Action

Neither state LED was lit red

when the EPO switch was

engaged.

• Check the wiring to your EPO switch.

• Check to make sure the EPO DIP switch

configuration is correct for your switch

(NO or NC). See step 2 on the previous page for

proper configuration instructions.

Only one of the state LEDs was lit

red when the EPO switch was

engaged.

• Check to make sure the EPO DIP switch

configuration is correct for your switch

(NO or NC) and retest. See step 2 on the

previous page for proper configuration

instructions.

• If the switch is configured correctly and both

LEDs did not light red after retesting, contact

APC customer support (see the back cover of

this manual).

EPO Ready To Test

Active Alarm xxofxx