42
InfraStruXure Power Generation System
Stats
Statistics: 00 of 00
XX,XXXX
Reset
Reset All
Name of statistic here
Scroll through a list of items that accumulates after the statistics record is reset, including:
• Open Xfer Count: The number of open transfers since this statistic was reset.
• Closed Xfer Count: The number of closed transfers since this statistic was reset.
• Generator Fuel Used: The amount of fuel used since this statistic was reset.
• Source 1 Bad Count: The number of times Source 1 was not acceptable, as
defined in the Transfer Points menu, since this statistic was reset.
• S1 Low Volts Count: The number of times the Source 1 input voltage went
below the configured Low voltage Transfer Point on one or more of the phases
since this statistic was reset.
• S1 High Volts Count: The number of times the Source 1 input voltage exceeded
the configured High voltage Transfer Point on one or more of the phases since
this statistic was reset.
• S1 Bad Freq Count: The number of times the Source 1 input voltage went
outside the configured Freq range, as defined in the Transfer Points menu, since
this statistic was reset.
• S1 Imbalance Count: The number of times the percent voltage difference
between two phases, as defined by the Phase Balance setting in the Transfer
Points menu, was exceeded on Source 1 since this statistic was reset.
• Total Time S1 Bad: The total amount of time Source 1 was not acceptable, as
defined in the Transfer Points menu, since this statistic was reset.
• Maximum Time S1 Bad: The longest amount of time Source 1 was not
acceptable, as defined in the Transfer Points menu, since this statistic was reset.
• Minimum Time S1 Bad: The shortest amount of time Source 1 was not
acceptable, as defined in the Transfer Points menu, since this statistic was reset.
• Time on Source 1: The total amount of time Source 1 was selected since this
statistic was reset.
• Time on Source 2: The total amount of time Source 2 was selected since this
statistic was reset.