ATS/Voltage

34

InfraStruXure Power Generation System

S2-Generator

One of the following is displayed to describe the condition of the input from Source 2.

OK

Source 2 is acceptable, as defined in the Transfer Points menu (the generator is
running).

OFF

The generator is not running.

BAD

Source 2 is not acceptable, as defined in the Transfer Points menu, even though the ATS
is commanding the generator to run.

Press

E

NTER

when the selector arrow rests at the S2-Generator item to display the following:

L1-2, L2-3, L3-1 The Source 2 line-to-line input voltage.

L1, L2, L3

The Source 2 line-to-neutral input voltage. These readings are only displayed on Wye
systems.

Frequency

The frequency of the Source 2 input, in hertz (Hz).

Qual

Describes the quality of the input from Source 2. One of the following conditions is
displayed:

Source Good: The source is acceptable, as defined in the Transfer Points menu.

Low Voltage: The input voltage is below the configured Low voltage Transfer Point

on one or more of the phases.

High Voltage: The input voltage exceeds the configured High voltage Transfer Point

on one or more of the phases.

Phase Imbalance: The percent voltage difference between two phases, as defined by

the Phase Balance setting in the Transfer Points menu, has been exceeded.

Freq Range: The frequency is outside the configured Freq range, as defined in the

Transfer Points menu.

Bad Rotation: The phase rotation does not match the configured Phase Sequence, as

defined in the Transfer Points menu.

Phase Sequence Lists the phase rotation (e.g., A-B-C) of the Source 2 input.