Emergency Manual Operation

InfraStruXure Power Generation System

25

How to return to powering the load from utility

1. Ensure the ATS Automatic Operation

switch is set to Disable.

2. Ensure the Source 1 switch is OFF (

).

3. Turn the Source 2 switch OFF (

):

a. Set the selector on the Source 2 switch

to Manual.

The operating lever will swing out

when the selector is set to Manual.

b. Turn the Source 2 switch

counterclockwise to OFF (

). Use the

operating lever key for easier

operation.

4. Turn the Source 1 switch ON (

):

a. Set the selector on the Source 1 switch

to Manual.

The operating lever will swing out

when the selector is set to Manual.

b. Turn the Source 1 switch clockwise to

ON (

). Use the operating lever key for

easier operation.

c. Close the operating levers on both the Source 1 and Source 2 switches, and then set the

selectors back to Auto to lock the switches in place.