2870b, Installation, Cable entry

background image

990-2870B

07/2006

*990-2870B*

APC Smart-UPS

®

VT ISX Enclosure

20-30 kVA 480V for 5 Battery Modules and

with Power Distribution Unit and

Isolation Transformer

Installation

IMPORTANT SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS

LOAD ON

LOAD ON

ON-BA

ON-BATTTT

BYPASS

ASS

FAUL

AULT

ESC

ESC

?

Warning

Always read the separate Safety Sheet 990-2822 prior to the
installation.

Warning

All electrical power and power control wiring must be installed by
a qualified electrician, and must comply with local and national
regulations for maximum power rating
.

Warning

The UPS must be supplied from a: 208Y/120V or 220Y/127V 4W+
GND 60 Hz source.

Note

Power terminal lug diameter: minimum 6 mm.
Torque value: 62 lbf

.

in/7 Nm.

1

Cable Entry

Cable entry takes place from the rear of the UPS. Pull out the lower end of
the handle and turn it counterclockwise to a horizontal position to open
the door.

Preparing for cabling (general)

Use a torx screwdriver to loosen the four M4 screws from the cable
landing cover and remove.

Preparing for bottom and top entry

Use a hammer to
punch out
knockouts and line
holes with
grommets (not
supplied).

Note

Make sure that the UPS is in its location of use before you
start the cabling.

Cable landing area

for AC input

Power Distribution

Unit (PDU)

Conduit box

Power module with

cable landings for

battery cables and

communication

cables

Smart-UPS® VT ISX w/transformer and PDU, 20-30 kVA, 480 V, Installation

Preparing for top cable entry

From the rear of the inside of the UPS push the top cover

spring locks

backwards to lift up the rear end of the top cover.

Slide out the top cover (mind the wing on either side of the plate).

Punch holes in labeled area between the two rails on the rear of the
top cover for conduits as required. Line hole(s) with grommets (not
supplied). Reinstall the top plate.

2

AC and Ground Cable

Landings

Bottom cable entry

Feed the input cables
in conduits (not
supplied) through the
punched holes in the
bottom plate.

Use cable ties to
attach the cables to
the slotted plate.

Connect the input
cables (L1, L2, L3),
to the cable landings.

Connect the ground cable using the provided screw (earth symbol
beneath the applicable screw).

Reinstall bottom cable landing cover.

Rear

L1

L2

L3