Ront, Anel, Isplay – Red Lion PAX2D User Manual

Page 8: Verview, 3 user input wiring, Setpoint annunciators, 7 prescaler output wiring (npn o.c.)

background image

8

4.3 USER INPUT WIRING

If User Input 1 and/or 2 are wired for quadrature or directional counting, an additional switching device should not be

connected to that User Input terminal. User Input terminal does not need to be wired in order to remain in inactive state.

Sourcing Logic (USrACt HI)

When the USrACt parameter is programmed

to HI, the user inputs of the meter are

internally pulled down to 0 V with 20 KW

resistance. The input is active when a

voltage greater than 2.2 VDC is applied.

USER INPUTS

USER

3

USER

2

USER

1

COMM.

7

8

9

10

Sinking Logic (USrACt LO)

When the USrACt parameter is programmed

to LO, the user inputs of the meter are

internally pulled up to +3.3 V with 20 KW

resistance. The input is active when it is

pulled low (<1.1 V).

+

(30V max.)

SUPPLY

V

USER

3

USER

2

USER

1

COMM.

8

7

-

10

9

USER INPUTS

4.4 SETPOINT (ALARMS) WIRING
4.5 SERIAL COMMUNICATION WIRING
4.6 ANALOG OUTPUT WIRING

See appropriate plug-in card bulletin for wiring details.

5.0 f

rOnT

p

anel

K

eys

a

nd

d

isplay

O

verview

Programmable Units Display

Display Line 1

Display Line 2

1

3

2

4

Setpoint Annunciators

KEY

DISPLAY MODE OPERATION

PROGRAMMING MODE OPERATION

D

Index through enabled Line 2 display values

Return to the previous menu level (momentary press)

Quick exit to Display Mode (press and hold)

P

Enter full programming mode or access the parameter and

hidden display loops; Press and hold to skip parameters and

go directly to Code or Programming Menu

Access the programming parameter menus, store selected parameter

and index to next parameter

!

User programmable Function key 1; hold for 3 seconds for

user programmable second function 1

Index through enabled Line 1 values (factory setting)

Increment selected parameter value; Hold

!

and momentarily press

@

key to increment next decade or

D key to increment by 1000’s

@

User programmable Function key 2; hold for 3 seconds for

user programmable second function 2

Reset Line 1 (factory setting)

Decrement selected parameter value; Hold

@

and momentarily press

!

key to decrement next decade or

D key to decrement by 1000’s

DISPLAY LINE 1

Line 1 is the large, 6-digit top line display. Counter values, rate values and the

maximum (Hi) and minimum (Lo) rate capture values can be shown on Line 1.

The 3-digit Units mnemonic characters can be used to indicate which Line 1

display value is shown. Standard or custom mnemonics are available for the

Line 1 values. See Line 1 parameters in the Display Parameters programming

section for configuration details.

DISPLAY LINE 2

Line 2 is the smaller, 9-digit bottom line display. Counter values, rate values,

rate capture values, setpoint values and parameter List A/B status can all be

shown on the Line 2 display. The display loops described below are used to

view, reset and modify the selected display values, based on the Line 2 Value

Access setting programmed for each available value. See Line 2 parameters in

the Display Parameters programming section for configuration details.

PS OU

T

COMM

7

11

-

+

4.7 PRESCALER OUTPUT WIRING

(NPN O.C.)