Pax2d frerquently used modbus register table – Red Lion PAX2D User Manual

Page 26

background image

26

REGISTER

ADDRESS

REGISTER NAME

LOW LIMIT

HIGH LIMIT

FACTORY

SETTING

ACCESS

COMMENTS

FREQUENTLY USED REGISTERS

40001

Counter A Value (Hi word)

-199999999 999999999

0

Read/Write

40002

Counter A Value (Lo word)

40003

Counter B Value (Hi word)

-199999999 999999999

0

Read/Write

40004

Counter B Value (Lo word)

40005

Counter C Value (Hi word)

-199999999 999999999

0

Read/Write

40006

Counter C Value (Lo word)

40007

Rate A Value (Hi word)

N/A

N/A

N/A

Read Only

40008

Rate A Value (Lo word)

40009

Rate B Value (Hi word)

N/A

N/A

N/A

Read Only

40010

Rate B Value (Lo word)

40011

Rate C Value (Hi word)

N/A

N/A

N/A

Read Only

40012

Rate C Value (Lo word)

40013

Max (Hi) Value (Hi word)

-199999

999999

0

Read/Write

40014

Max (Hi) Value (Lo word)

40015

Min (Lo) Value (Hi word)

-199999

999999

0

Read/Write

40016

Min (Lo) Value (Lo word)

40017

Setpoint 1 Value (Hi word)

-199999

999999

100

Read/Write Active List (A or B)

40018

Setpoint 1 Value (Lo word)

40019

Setpoint 2 Value (Hi word)

-199999

999999

200

Read/Write Active List (A or B)

40020

Setpoint 2 Value (Lo word)

40021

Setpoint 3 Value (Hi word)

-199999

999999

300

Read/Write Active List (A or B)

40022

Setpoint 3 Value (Lo word)

40023

Setpoint 4 Value (Hi word)

-199999

999999

400

Read/Write Active List (A or B)

40024

Setpoint 4 Value (Lo word)

40025

Counter A Scale Factor (Hi word)

1

999999

100000

Read/Write Active List (A or B)

40026

Counter A Scale Factor (Lo word)

40027

Counter B Scale Factor (Hi word)

1

999999

100000

Read/Write Active List (A or B)

40028

Counter B Scale Factor (Lo word)

40029

Counter C Scale Factor (Hi word)

1

999999

100000

Read/Write Active List (A or B)

40030

Counter C Scale Factor (Lo word)

40031

Counter A Count Load (Hi word)

-199999

999999

500

Read/Write Active List (A or B)

40032

Counter A Count Load (Lo word)

40033

Counter B Count Load (Hi word)

-199999

999999

500

Read/Write Active List (A or B)

40034

Counter B Count Load (Lo word)

40035

Counter C Count Load (Hi word)

-199999

999999

500

Read/Write Active List (A or B)

40036

Counter C Count Load (Lo word)

40037

Setpoint Output Register (SOR)

0

15

N/A

Read/Write

Status of Setpoint Outputs. Bit State: 0=Off, 1=On.

Bit 3 = S1, Bit 2 = S2, Bit 1 = S3, Bit 0 = S4.

Outputs can only be activated/reset with this register when the

respective bits in the Manual Mode Register (MMR) are set.

40038

Manual Mode Register (MMR)

0

31

0

Read/Write Bit State: 0 = Auto Mode, 1 = Manual Mode Bit 4 = S1, Bit 3 =

S2, Bit 2 = S3, Bit 1 = S4, Bit 0 = Linear Output

40039

Reset Output Register

0

15

0

Read/Write Bit State: 1= Reset Output, bit is returned to zero following

reset processing; Bit 3 = S1, Bit 2 = S2, Bit 1 = S3, Bit 0 = S4

40040

Analog Output Register (AOR)

0

4095

0

Read/Write Linear Output Card written to only if Linear Output is in Manual

Mode (MMR bit 0 = 1).

PAX2D FRERQUENTLY USED MODBUS REGISTER TABLE

Only frequently used registers are shown below. The entire Modbus Register Table can be found at www.redlion.net.

Values less than 65,535 will be in (Lo word). Values greater than 65,535 will continue into (Hi word). Negative values are represented by two’s complement of the

combined (Hi word) and (Lo word).

Note 1: The PAX2D should not be powered down while parameters are being changed. Doing so may corrupt the non-volatile memory resulting in checksum errors.