Pax2d frerquently used modbus register table – Red Lion PAX2D User Manual
Page 26

26
REGISTER
ADDRESS
REGISTER NAME
LOW LIMIT
HIGH LIMIT
FACTORY
SETTING
ACCESS
COMMENTS
FREQUENTLY USED REGISTERS
40001
Counter A Value (Hi word)
-199999999 999999999
0
Read/Write
40002
Counter A Value (Lo word)
40003
Counter B Value (Hi word)
-199999999 999999999
0
Read/Write
40004
Counter B Value (Lo word)
40005
Counter C Value (Hi word)
-199999999 999999999
0
Read/Write
40006
Counter C Value (Lo word)
40007
Rate A Value (Hi word)
N/A
N/A
N/A
Read Only
40008
Rate A Value (Lo word)
40009
Rate B Value (Hi word)
N/A
N/A
N/A
Read Only
40010
Rate B Value (Lo word)
40011
Rate C Value (Hi word)
N/A
N/A
N/A
Read Only
40012
Rate C Value (Lo word)
40013
Max (Hi) Value (Hi word)
-199999
999999
0
Read/Write
40014
Max (Hi) Value (Lo word)
40015
Min (Lo) Value (Hi word)
-199999
999999
0
Read/Write
40016
Min (Lo) Value (Lo word)
40017
Setpoint 1 Value (Hi word)
-199999
999999
100
Read/Write Active List (A or B)
40018
Setpoint 1 Value (Lo word)
40019
Setpoint 2 Value (Hi word)
-199999
999999
200
Read/Write Active List (A or B)
40020
Setpoint 2 Value (Lo word)
40021
Setpoint 3 Value (Hi word)
-199999
999999
300
Read/Write Active List (A or B)
40022
Setpoint 3 Value (Lo word)
40023
Setpoint 4 Value (Hi word)
-199999
999999
400
Read/Write Active List (A or B)
40024
Setpoint 4 Value (Lo word)
40025
Counter A Scale Factor (Hi word)
1
999999
100000
Read/Write Active List (A or B)
40026
Counter A Scale Factor (Lo word)
40027
Counter B Scale Factor (Hi word)
1
999999
100000
Read/Write Active List (A or B)
40028
Counter B Scale Factor (Lo word)
40029
Counter C Scale Factor (Hi word)
1
999999
100000
Read/Write Active List (A or B)
40030
Counter C Scale Factor (Lo word)
40031
Counter A Count Load (Hi word)
-199999
999999
500
Read/Write Active List (A or B)
40032
Counter A Count Load (Lo word)
40033
Counter B Count Load (Hi word)
-199999
999999
500
Read/Write Active List (A or B)
40034
Counter B Count Load (Lo word)
40035
Counter C Count Load (Hi word)
-199999
999999
500
Read/Write Active List (A or B)
40036
Counter C Count Load (Lo word)
40037
Setpoint Output Register (SOR)
0
15
N/A
Read/Write
Status of Setpoint Outputs. Bit State: 0=Off, 1=On.
Bit 3 = S1, Bit 2 = S2, Bit 1 = S3, Bit 0 = S4.
Outputs can only be activated/reset with this register when the
respective bits in the Manual Mode Register (MMR) are set.
40038
Manual Mode Register (MMR)
0
31
0
Read/Write Bit State: 0 = Auto Mode, 1 = Manual Mode Bit 4 = S1, Bit 3 =
S2, Bit 2 = S3, Bit 1 = S4, Bit 0 = Linear Output
40039
Reset Output Register
0
15
0
Read/Write Bit State: 1= Reset Output, bit is returned to zero following
reset processing; Bit 3 = S1, Bit 2 = S2, Bit 1 = S3, Bit 0 = S4
40040
Analog Output Register (AOR)
0
4095
0
Read/Write Linear Output Card written to only if Linear Output is in Manual
Mode (MMR bit 0 = 1).
PAX2D FRERQUENTLY USED MODBUS REGISTER TABLE
Only frequently used registers are shown below. The entire Modbus Register Table can be found at www.redlion.net.
Values less than 65,535 will be in (Lo word). Values greater than 65,535 will continue into (Hi word). Negative values are represented by two’s complement of the
combined (Hi word) and (Lo word).
Note 1: The PAX2D should not be powered down while parameters are being changed. Doing so may corrupt the non-volatile memory resulting in checksum errors.