beautypg.com

Dec pt, Sc fac, Scaler – Red Lion PAX2D User Manual

Page 11: Reset, Cnt ld, R p-up, Ps out, Ps scl

background image

11

Counter B Selections

SELECTION MODE

DESCRIPTION

NONE

None

Does not count.

bAtCH

Batch

Counter B internally counts the number of output

activations of the selected setpoint(s). The count

source is selected in the Yes/No sub-menu shown

for each setpoint (bAt S1 thru bAt S4).

Cnt

Count X1

Adds Input B falling edge.

dCntUd

Dual Count

X1 w/direction

Adds Input B falling edge if User 2 is high.

Subtracts Input B falling edge if User 2 is low.

dqUAd1

Dual Count

Quad X1

Adds Input B rising edge when User 2 is high.

Subtracts Input B falling edge when User 2 is high.

dqUAd2

Dual Count

Quad X2

Adds Input B rising edge when User 2 is high and

Input B falling edge when User 2 is low. Subtracts

Input B falling edge when User 2 is high and Input

B rising edge when User 2 is low.

Cnt2

Count X2

Adds Input B rising and falling edges.

dCtUd2

Dual Count

X2 w/direction

Adds Input B rising and falling edges if User 2 is

high. Subtracts Input B rising and falling edge if

User 2 is low.

Counter C Selections

SELECTION MODE

DESCRIPTION

NONE

None

Does not count.

Cnt A

Counter A

Counter C counts the incoming pulses from Counter A

input as per Counter A mode of operation. The signal

is scaled only according to Counter C parameters.

Cnt b

Counter B

Counter C counts the incoming pulses from Counter B

input as per Counter B mode of operation. The signal

is scaled only according to Counter C parameters.

Add Ab

Counter A +

Counter B

Counter C counts the incoming pulses from Counter A

and B inputs as per Counter A and B modes of

operation. The result is scaled only according to

Counter C parameters. (Example: If Counter A is set

for Count X1 mode and Counter B is set for Count X2

mode, then Counter C will increment by 1 for each

pulse received on Input A and increment by 2 for each

pulse received on Input B. Counter C scale settings

are then applied and the result displayed.)

Sub Ab

Counter A –

Counter B

Counter C counts the incoming pulses from Counter A

and B inputs as per Counter A and B modes of

operation and subtracts the B counts from the A

counts. The result is scaled only according to Counter

C parameters. (Example: If Counter A is set for Count

X1 mode and Counter B is set for Count X2 mode,

then Counter C will increment by 1 for each pulse

received on Input A and decrement by 2 for each pulse

received on Input B. Counter C scale settings are then

applied and the result displayed.)

Note: Counter A, B and C must all be reset at the same time for the math to be

performed on the display values.

bAtCH

Batch

Counter C internally counts the number of output

activations of the selected setpoint(s). The count

source is selected in the Yes/No sub-menu shown for

each setpoint (bAt S1 thru bAt S4).

SLAUE

Slave

Counter C functions as a serial slave display. See

Serial Communications section for details.

COUNTER DECIMAL POSITION

0

0.00

0.0000

0.0

0.000

0.00000

This selects the decimal point position for the selected counter, and any

setpoint value assigned to that counter. The selection will also affect that

counter’s scale factor calculations.

COUNTER SCALE FACTOR

0.00001

to

9.99999

The number of input counts for the selected counter is multiplied by the scale

factor and the scale multiplier to obtain the desired process value. A scale factor

of 1.00000 will result in the display of the actual number of input counts. For





and

 

modes of operation, the math is performed on the input signals

and then the result is scaled by Counter C scaling. To achieve correct results,

both Input A and Input B must provide the same amount of pulses per unit of

measurement. (Details on scaling calculations are explained at the end of this

section.) Scale Factor values can also be entered during Program Lockout, if

enabled in the Parameter Display loop. See “Line 2 Display Access” in the Display

Parameter Module.

COUNTER SCALE MULTIPLIER

10

1

0.1

0.01

The number of input counts for the selected counter is multiplied by the scale

multiplier and the scale factor to obtain the desired process value. (Details on

scaling calculations are explained at the end of this section.)

COUNTER RESET ACTION

ZErO

Cnt Ld

When the selected counter is reset, it returns to zero or the counter count load

value. This reset action applies to all selected counter resets, except a setpoint

generated counter auto reset programmed in the Setpoint Output Parameter

Module.

COUNTER COUNT LOAD VALUE

-199999

to

999999

When Reset To Count Load action is chosen, the selected counter will reset

to this value. Count Load values can also be entered during Program Lockout,

if enabled in the Parameter Display loop. See “Line 2 Display Access” in the

Display Parameter Module.

COUNTER RESET AT POWER-UP

NO

YES

The selected counter may be programmed to reset at each meter power-up.

The next two parameters will only appear when programming Counter A.

PRESCALER OUTPUT ENABLE

NO

YES

This enables the prescaler output. The prescaler output is useful for providing

a lower frequency scaled pulse train to a PLC or another external counter. On

each falling edge of Input A, the prescaler output register increments by the

prescaler scale value (PS SCL). When the register equals or exceeds 1.0000, a

pulse is output and the register is lowered by 1.0000. The prescaler register is

reset to zero whenever Counter A is reset (except for Setpoint Counter Auto

Reset). (See Prescaler Output Figure.)

PRESCALER SCALE VALUE

0.0001

to

1.0000

The prescaler output frequency is the Input A frequency times the prescaler

scale value.

PRESCALER OUTPUT FIGURE

dEC Pt

0

Ct

x

1

3

2

4

SC FAC

1.00000

Ct

x

1

3

2

4

SCALEr

1

Ct

x

1

3

2

4

RESEt

ZErO

Ct

x

1

3

2

4

Cnt Ld

500

Ct

x

1

3

2

4

R P-UP

N0

Ct

x

1

3

2

4

PS OUt

NO

IPA

1

3

2

4

PS SCL

1.0000

IPA

Prescaler Output Value = 0.25