beautypg.com

Diagnostic sub-functions, Table 43, Dmt340 modbus diagnostics – Vaisala DMT340 User Manual

Page 189

background image

Appendix B _________________________________________________________ Modbus Reference

VAISALA _______________________________________________________________________ 187

Diagnostic Sub-Functions

DMT340 supports some of the Modbus diagnostic functions described in
the Modbus Application Protocol Specification V1.1b. These diagnostic
functions are accessed with function code 08. See Table 43 below for
details.

Table 43

DMT340 Modbus Diagnostics

Code

Sub-Function Name

Notes

00 (0x00)

Return Query Data

01 (0x01)

Restart Communications
Option

Cancels the “Listen Only” mode.

Data field must be set to “00 00”
for Restart Communications
Option. Sub-Function 01 with
data field “FF 00” is rejected.

02 (0x02)

Return Diagnostic Register

Non-zero if there are active
transmitter errors.

For same error information, see
status registers 0516 and 0517.
The value of the Diagnostic
Register is a logical OR of these
two status registers.

04 (0x04)

Force Listen Only Mode

Puts device “off-line”

10 (0x0A)

Clear Counters and
Diagnostic Register

Diagnostic Register cannot be
cleared

11 (0x0B)

Return Bus Message Count

Total number of messages seen
on the bus/interface

12 (0x0C)

Return Bus Communication
Error Count

Number of messages with bad
Modbus RTU CRC or Modbus
TCP frame

13 (0x0D)

Return Bus Exception Error
Count

Number of Modbus exception
responses sent

14 (0x0E)

Return Slave Message Count Number of Modbus messages

processed

15 (0x0F)

Return Slave No Response
Count

Number of Modbus messages
received without sending a
response. This happens for
received broadcast messages
(Modbus RTU only) or when
DMT340 is in the “Listen Only”
mode.


Although Modbus Diagnostics are standardized only for serial line
devices, DMT340 supports the same diagnostic functions also on
Modbus TCP.

NOTE

Resetting, powering up the transmitter, or reselecting the Modbus mode
(by serial command or with the user interface) resets all Modbus
diagnostic counters and cancels any “Listen Only” mode.