Appendix B _________________________________________________________ Modbus Reference

VAISALA _______________________________________________________________________ 185

Status Registers (Read-Only)

Table 39

Status Registers

Name

Address

Description

Fault status

0513

1 = No errors

Online status

0514

1 = Online data available

Error code (bits 15…0)

0516

Bit field that represents the
error codes listed in Table 32
on page 151. Active errors are
set to 1. For example, if bit 14
is set to 1, error code E14 is
active.

Error code (bits 31…16)

0517


Error information can retrieved also with function code 08, sub-function
02.

NOTE

Basic status information of the DMT340 transmitter is also available with
the Read Exception Status function code 07. For details, see section
Exception Status Outputs on page 186.

Configuration Registers

Configuration parameter registers are used to configure the measurement.
Writing out-of-range values is silently ignored.

Table 40

Configuration Parameter Registers

Name

Float

Integer

Valid Range

Pressure setting default
value

0769…0770

1025 (×1)

0…9999 hPa

Pressure setting
temporary value

0771…0772

1026 (×1)

0…9999 hPa

Sensor purge interval

0773…0774

1027 (×1)

10…2880 min

Molecular weight for
ppm

w

calculation

0775…0776

1028 (×0.001)

0…999.999
g/mol


If you modify the pressure setting repeatedly, modify the temporary
value at register 0771...0772 (1026) instead of the permanent setting at
register 0769…0770 (1025). Set the temporary value to zero to return to
the default pressure setting.

Non-metric units are not available on Modbus. If they are needed,
calculate the conversion outside the transmitter.