beautypg.com

Fresh air openings for confined spaces – A.O. Smith 3400 User Manual

Page 23

background image

23

CONFINED SPACE

A confined space is one whose volume is less than 50 cubic

feet per 1,000 Btu/hr (4.8 cubic meters per kW) of the total input

rating of all appliances installed in the space.
Openings must be installed to provide fresh air for combustion,

ventilation and dilution in confined spaces. The required size for

the openings is dependent on the method used to provide fresh

air to the confined space and the total Btu/hr input rating of all

appliances installed in the space.

DIRECT VENT APPLIANCES
Appliances installed in a direct vent configuration that derive all

air for combustion from the outdoor atmosphere through sealed

intake air piping are not factored in the total appliance input Btu/

hr calculations used to determine the size of openings providing

fresh air into confined spaces.

EXHAUST FANS
Where exhaust fans are installed, additional air shall be provided

to replace the exhausted air. When an exhaust fan is installed

in the same space with a water heater, sufficient openings to

provide fresh air must be provided that accommodate the

requirements for all appliances in the room and the exhaust fan.

Undersized openings will cause air to be drawn into the room

through the water heater’s vent system causing poor combustion.

Sooting, serious damage to the water heater and the risk of fire

or explosion may result. It can also create a risk of asphyxiation.

LOUVERS AND GRILLES
The free areas of the fresh air openings in the instructions that

follow do not take in to account the presence of louvers, grilles or

screens in the openings.
The required size of openings for combustion, ventilation and

dilution air shall be based on the “net free area” of each opening.

Where the free area through a design of louver or grille or screen

is known, it shall be used in calculating the size of opening

required to provide the free area specified. Where the louver and

grille design and free area are not known, it shall be assumed

that wood louvers will have 25% free area and metal louvers and

grilles will have 75% free area. Non motorized louvers and grilles

shall be fixed in the open position.

FRESH AIR OPENINGS FOR CONFINED SPACES

The following instructions shall be used to calculate the size,

number and placement of openings providing fresh air for

combustion, ventilation and dilution in confined spaces. The

illustrations shown in this section of the manual are a reference

for the openings that provide fresh air into confined spaces

only. Do not refer to these illustrations for the purpose of vent

installation. See Venting section on Page 25 for complete venting

installation instructions.

OUTDOOR AIR THROUGH TWO OPENINGS

The confined space shall be provided with two permanent

openings, one commencing within 12 inches (300 mm) of the top

and one commencing within 12 inches (300 mm) of the bottom of

the enclosure. The openings shall communicate directly with the

outdoors. See Figure 17.
Each opening shall have a minimum free area of 1 square inch

per 4,000 Btu/hr (550 mm

2

per kW) of the aggregate input rating

of all appliances installed in the enclosure. Each opening shall

not be less than 100 square inches (645 cm

2

).

OUTDOOR AIR THROUGH ONE OPENING

Alternatively a single permanent opening, commencing within 12

inches (300 mm) of the top of the enclosure, shall be provided.

See Figure 18. The water heater shall have clearances of at

least 1 inch (25 mm) from the sides and back and 6 inches (150

mm) from the front of the appliance. The opening shall directly

communicate with the outdoors or shall communicate through a

vertical or horizontal duct to the outdoors or spaces that freely

communicate with the outdoors and shall have a minimum free

area of the following:
1. 1 square inch per 3000 Btu/hr (700 mm

2

per kW) of the total

input rating of all appliances located in the enclosure, and

2. Not less than the sum of the areas of all vent connectors in

the space.

FIGURE 17. OUTDOOR AIR THROUGH TWO OPENINGS

FIGURE 18. OUTDOOR AIR THROUGH ONE OPENING

This manual is related to the following products: