A.O. Smith 3400 User Manual

Page 62

background image

62

CODE

DESCRIPTION

RECOMMENDED TROUBLESHOOTING OF

LOCKOUT CODES

NOTE

94

Header sensor fault

1. Check wiring and correct any possible errors.

2. Replace the header sensor.

3. If previous steps are correct and fault persists,

replace the module.

H

95

Stack sensor fault

1. Check wiring and correct any possible errors.

2. Replace the stack sensor.

3. If previous steps are correct and fault persists,

replace the module.

H

96

Outdoor sensor fault

1. Check wiring and correct any possible errors.

2. Replace the outdoor sensor.

3. If previous steps are correct and fault persists,

replace the module.

H

97

Internal Fault: A2D mismatch.

Internal Fault.

1. Reset Module.

2. If fault repeats, replace module.

L

98

Internal Fault: Exceeded VSNSR voltage

L

99

Internal Fault: Exceeded 28V voltage tolerance

L

100

Pressure Sensor Fault

1. Verify the Pressure Sensor is a 4-20 ma source.

2. Check wiring and correct any possible errors.

3. Test Pressure Sensor for correct operation.

4. Replace the Pressure sensor.

5. If previous steps are correct and fault persists,

replace the module.

H

101-104 RESERVED

Flame Operation Faults

105

Flame detected out of sequence

1. Check that flame is not present in the combustion

chamber. Correct any errors.

2. Make sure that the flame detector is wired to the

correct terminal.

3. Make sure the F & G wires are protected from

stray noise pickup.

4. Reset and sequence the module, if code

reappears, replace the flame detector.

5. Reset and sequence the module, if code

reappears, replace the module.

H or L

106

Flame lost in MFEP

1. Check pilot valve (Main Valve for DSI) wiring and

operation - correct any errors.

2. Check the fuel supply.

3. Check fuel pressure and repeat turndown tests.

4. Check ignition transformer electrode, flame

detector, flame detector siting or flame sensor

position.

5. If steps 1 through 4 are correct and the fault

persists, replace the module.

L

107

Flame lost early in run

L

108

Flame lost in run

L

109

Ignition failed

L

110

Ignition failure occurred

Hold time of recycle and hold option. Will not be a

lockout fault. Hold Only.

H

111

Flame current lower than WEAK threshold

Internal hardware test. Not a lockout,

H

112

Pilot test flame timeout

Interrupted Pilot or DSI application and flame lost

when system in “test” mode.

1. Reset the module to restart.

L

113

Flame circuit timeout

Flame sensed during Initiate or off cycle, hold 240

seconds, if present after 240 seconds, lockout.

L

114-116

RESERVED

117

Condensate Fault

1. Check the condensate trap at the back of the

boiler for any blockage.

2. Check the exhaust vent piping for any blockage.

L

118-121

RESERVED
Rate Proving Faults