beautypg.com

General requirements, Location – A.O. Smith 3400 User Manual

Page 21

background image

21

GENERAL REQUIREMENTS

REQUIRED ABILITY

Installation or service of this boiler requires ability equivalent

to that of a qualified service technician in the field involved.

Plumbing, air supply, venting, gas supply, and electrical work are

re quired.

LOCATION

When installing the boiler, consideration must be given to proper

location. The location selected should provide ade quate air

supply and be as centralized with the piping system as possible.

This boiler is intended for Indoor Installation only, and should not

be installed where freezing temperatures or any moisture could

damage the external components of the boiler.

REPLACING EXISTING COMMON VENTED BOILER

NOTE: This section does not describe a method for common

venting XB units. It describes what must be done when a unit

is removed from a common vent system. The XB units require

special vent systems and fans for common vent.
When an existing boiler is removed from a common venting

system, the common venting system is likely to be too large

for proper venting of the appliances remaining connected to it.

At the time of removal of an existing boiler, the following steps

should be followed with each appliance remaining connected to

the common venting system placed in operation, while the other

appliances remaining connected to the common venting system

are not in operation.

1. Seal any unused openings in the common venting system.
2. Visually inspect the venting system for proper size and

horizontal pitch and determine there is no blockage or

restriction, leakage, corrosion and deficiencies which could

cause an unsafe condition.

3. In so far as it is practical, close all building doors and

windows and all doors between the space in which the

appliances remaining connected to the common venting

system are located and other spaces of the building. Turn

on clothes dryers and any appliance not connected to the

common venting system. Turn on any exhaust fans, such as

range hoods and bathroom exhausts, so they will operate

at maximum speed. Do not operate a summer exhaust fan.

Close fireplace dampers.

4. Place in operation the appliance being inspected. Follow the

lighting instructions. Adjust thermostat so the appliance will

operate continuously.

5. Test for spillage at the draft hood relief opening after 5

minutes of main burner operation. Use the flame of a match

or candle, or smoke from a cigarette, cigar or pipe.

6. After it has been determined that each appliance remaining

connected to the common venting system properly vents

when tested as outlined above, return doors, windows,

exhaust fans, fireplace dampers and any other gas-burning

appliance to their previous condition of use.

7. Any improper operation of the common venting system

should be corrected so that the installation conforms with

the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/

or CSA B149.1, Installation Codes. When resizing any

portion of the common venting system, the common venting

system should be resized to approach the minimum size as

determined using the appropriate tables and guidelines in the

National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CSA

B149.1, Installation Codes.

This manual is related to the following products: