beautypg.com

A.O. Smith 3400 User Manual

Page 16

background image

16

CIRCULATING PUMP
A circulating pump is used when a system requires a circulating

loop or there is a buffer tank used in conjunction with the boiler.

Install in accordance with the current edition of the National

Electrical Code, NFPA 70 or the Canadian Electrical Code,

CSA C22.1. All bronze circulating pumps are recommended

for use with commercial boilers. Some circulating pumps are

manufactured with sealed bearings and do not require further

lubrication. Some circulating pumps must be periodically oiled.

Refer to the pump manufacturer’s instructions for lubrication

requirements.
XB HYDRONIC BOILERS: The circulating pump is not provided

on standard models (optional) and must be obtained and installed

in the field.
PRIMARY SYSTEM CONTROL
All XB boiler installations require a “Primary System Control” that

senses and reacts to water temperature inside the return line

on primary/secondary hydronic heating systems. The Primary

System Control will activate and deactivate boiler heating cycles

based on its setpoint and current system water temperature.

There are three suitable methods to configure a Primary System

Control. One of these three methods must be used.

1. The Primary System Control can be the boiler’s control

system working with the factory supplied Header Sensor,

installed in the return line on primary/secondary hydronic

heating systems.
2. Alternatively, the Burner Control system can be used

as a Primary System Control. It will also provide boiler status

and error reporting. Multiple boilers can be joined together

to heat a system instead of a single, larger burner or boiler.

Using boilers in parallel is more efficient, costs less, reduces

emissions, improves load control, and is more flexible than

the traditional large boiler.
3. MB2 and COM2 ports can be used for Building

Management Systems.

INTERNAL CONTAMINANTS

The hydronic system must be internally cleaned and flushed

after a new or replacement boiler has been installed, to remove

contaminants that may have accumulated during installation.

This is extremely important when a replacement boiler is installed

into an existing system where Stop Leak or other boiler additives

have been used.
Failure to clean and flush the system can produce acid

concentrations that become corrosive, and leads to heat

exchanger failure.
All hot water heating systems should be completely flushed with

a grease removing solution to assure trouble-free opera tion. Pipe

joint compounds, soldering paste, grease on tubing and pipe all

tend to contaminate a system
Failure to flush contaminants from a system can cause solids

to form on the inside of boiler exchangers, create excessive

blockage of water circulation, deterioration of the pump seals

and impellers.

HOT WATER BOILER SYSTEM - GENERAL WATER

LINE CONNECTIONS

Piping diagrams will serve to provide the installer with a

reference for the materials and methods of piping necessary for

installation. It is essential that all water piping be installed and

connected as shown on the diagrams. Check the diagrams to

be used thoroughly before starting installation to avoid possible

errors and to minimize time and material cost. It is essential that

all water piping be installed and connected as shown on the

diagrams. See Figure 75 on Page 78.

CLOSED WATER SYSTEMS

Water supply systems may, because of code requirements

or such conditions as high line pressure, among others, have

installed devices such as pressure reducing valves, check

valves, and back flow preventers. Devices such as these cause

the water system to be a closed system.

THERMAL EXPANSION

As water is heated, it expands (thermal expansion). In a closed

system the volume of water will increase when it is heated. As the

volume of water increases there will be a corresponding increase

in water pressure due to thermal expansion. Thermal expansion

can cause premature failure (leakage). This type of failure is not

covered under the limited warranty. Thermal expansion can also

cause intermittent Temperature-Pressure Relief Valve operation:

water discharged from the valve due to excessive pressure build

up. This condition is not covered under the limited warranty.

The Temperature-Pressure Relief Valve is not intended for the

constant relief of thermal expansion.
A properly sized thermal expansion tank must be installed on

all closed systems to control the harmful effects of thermal

expansion. Contact a local plumbing service agency to have a

thermal expansion tank installed.

PRESSURE RELIEF VALVE

An ASME rated pressure relief valve is furnished with the boiler.

A fitting for the relief valve is provided in the top of the boiler.

Never operate the heating elements without being certain the

boiler is filled with water and a properly sized pressure relief

valve is installed in the relief valve opening provided.
The pressure rating of the relief valve should be equal to or less

than the rated pressure capacity of any component in the system

including the boiler. Should the valve need to be replaced, call

the toll free phone number listed on the back of this manual for

further technical assistance

This manual is related to the following products: