60

CODE

DESCRIPTION

RECOMMENDED TROUBLESHOOTING OF

LOCKOUT CODES

NOTE

30

Internal fault: Flame bias shorted to adjacent pin

Internal Fault.

1. Reset Module.

2. If fault repeats, replace module.

H

31

Internal fault: SLO electronics unknown error

H

32 - 46

Internal fault: Safety Key 0 through 14

L

System Errors

47

Flame sensor to ground leakage

H

48

Static flame (not flickering)

H

49

24 VAC voltage low/high

1. Check the Module and display connections.

2. Check the Module power supply and make sure

that both frequency, voltage and VA meet the

specifications.

H

50

Modulation fault

Internal sub-system fault.

1. Review alert messages for possible trends.

2. Correct possible problems.

3. If fault persists, replace module.

H

51

Pump fault

H

52

Motor tachometer fault

H

53

AC inputs phase reversed

1. Check the Module and display connections.

2. Check the Module power supply and make

sure that both frequency and voltage meet the

specifications.

3. On 24 VAC applications, assure that J4-10 and

J8-2 are connected together.

L

54

Safety GVT model ID does not match application's

model ID

Contact the qualified service technician.

L

55

Application configuration data block CRC errors

Contact the qualified service technician.

L

56 - 57

RESERVED

58

Internal fault: HFS shorted to IAS

Internal Fault.

1. Reset Module.

2. If fault repeats, replace module.

L

59

Internal Fault: Mux pin shorted

L

Normal Event Status

60

Internal Fault: HFS shorted to LFS

L

61

Anti short cycle

Will not be a lockout fault. Hold Only.

H

62

Fan speed not proved

H

63

LCI OFF

1. Check wiring and correct any faults.

2. Check Interlocks connected to the LCI to assure

proper function.

3. Reset and sequence the module; monitor the LCI

status.

4. If code persists, replace the module.

H

64

PII OFF

1. Check wiring and correct any faults.

2. Check Preignition Interlock switches to assure

proper functioning.

3. Check the valve operation.

4. Reset and sequence the module; monitor the PII

status.

5. If code persists, replace the module.

H or L

65

Interrupted Airflow Switch OFF

1. Check wiring and correct any possible shorts.

2. Check airflow switches to assure proper

functioning.

3. Check the fan/blower operation.

4. Reset and sequence the module; monitor the

airflow status.

5. If code persists, replace the module.

H or L

66

Interrupted Airflow Switch ON

H or L