beautypg.com

Boiler start up and operations – A.O. Smith 3400 User Manual

Page 41

background image

41

BOILER START UP AND OPERATIONS

IMPORTANT

Only an A. O. Smith Certified Start-up agent must perform the

initial firing of the boiler. At this time the user should not hesitate

to ask the start-up agent any questions regarding the operation

and maintenance of the unit. If you still have questions, please

contact the factory or your local A. O. Smith representative.

Contact Technical Support noted on the back cover for the name

of your closest Certified Start-Up agent.
Lighting and Operating instructions are included with this manual.

By using these instructions, the user may be able to make minor

operational adjustments and save unnecessary service calls.

However the user should not attempt repairs, but should contact

a qualified service technician or gas supplier.

GENERAL

Never operate the boiler without first making sure the boiler and

system are filled with water, in addition:

• Make sure a temperature and pressure relief valve

is installed in the storage tank for hot water supply

installations.

• Make sure that the boiler and system have been purged

of air and checked for leaks.

Also ensure to check the gas piping for leaks before beginning

the initial firing of the boiler.

FILLING AND PURGING OF HEATING BOILER

INSTALLATION

1. Fast fill system through bypass until pressure approaches

desired system pressure. Close bypass valve and permit

pressure to be established by the pressure reducing valve.

2. Vent all high points in system to purge system of air.
Provisions should be made to permit manual venting of radiators

or convectors.

PURGING GAS LINE

Gas line purging is required with new piping or systems in which

air has entered.

INLET GAS PRESSURE

The inlet gas pressure is measured by removing the 1/8” NPT Plug

located on the upstream side of the supply gas control valve, and

insert a 1/8” NPT hose barb fitting to be connected to a manometer

or pressure gauge. Once pressure has been checked and/or

adjusted, replace the plug and check for leaks. The maximum value

specified in Table 2 on Page 6 must not be exceeded. The minimum

values, shown in Table 2, must be maintained under both load and

no load conditions (static and firing conditions). The combination

gas control valves supplied with the boiler are for low pressure

service. If upstream pressure exceeds 14.0” W.C., an intermediate

gas pressure regulator of the lockup type must be installed.

MANIFOLD PRESSURE CONNECTIONS

Check the manifold pressure (refer to Table 2 on Page 6) by

removing the pipe plug (located on the back of the boiler near

the main gas shutoff valve, see Figure 40) and inserting a

suitable 1/8” NPT hose barb for connection to the manometer/

pressure gauge. Upon completion of measurements and

adjustments, remove the hose barb and replace the pipe plug.

Check for gas leaks and insure all connections are gas tight,

see Figure 41.

FREEZE PROTECTION (HYDRONIC HEATING

INSTALLATION)

1. Determine freeze protection fluid quantity using system

water content, following fluid manufacturer’s instructions.

2. Local codes may require a backflow preventer or actual

disconnect from city water supply.

3. When using freeze protection fluid with automatic fill, install

a water meter to monitor water makeup. Freeze protection

fluid may leak before the water begins to leak, causing

concentration to drop, reducing the freeze protection level.

INSPECT/FILL CONDENSATE SYSTEM
Inspect/check condensate lines and fittings:

1. Inspect the condensate drain line, condensate PVC fittings

and condensate trap. Repair any leaks.

Fill condensate trap with water:

1. Remove the 2 inch PVC cap with the switch located at the

top of the trap.

2. Fill with fresh water until the water begins to pour out of the

drain.

3. Replace the cap. Press the cap onto the trap until the cap

makes contact with the drain.

The condensate trap must be filled with water during all times of

boiler operation to avoid flue gas emission from the condensate

drain line. Failure to fill the trap could result in severe personal

injury or death.

FIGURE 41. GAS TRAIN ASSEMBLY

BURNER

FLAPPER

BLOWER

VENTURI

GAS PRESSURE
SWITCH

FLEX GAS
MANIFOLDS

MANUAL GAS
SHUTOFF VALVE

MODULATING
GAS VALVE

DIFFERENTIAL
MANIFOLD
PRESSURE TAP

This manual is related to the following products: