61

CODE

DESCRIPTION

RECOMMENDED TROUBLESHOOTING OF

LOCKOUT CODES

NOTE

67

ILK OFF

1. Check wiring and correct any possible shorts.

2. Check Interlock (ILK) switches to assure proper

function.

3. Verify voltage through the interlock string to the

interlock input with a voltmeter.

4. If steps 1-3 are correct and the fault persists,

replace the module.

H or L

68

ILK ON

H or L

69

Pilot test hold

1. Verify Run/Test is changed to Run.

2. Reset Module.

3. If fault repeats, replace module.

H

70

Wait for leakage test completion

1. Internal Fault. Reset Module.

2. If fault repeats, replace module.

H

71 - 77

RESERVED

78

Demand Lost in Run

1. Check wiring and correct any possible errors.

2. If previous steps are correct and fault persists,

replace the module.

H

79

Outlet high limit

1. Check wiring and correct any possible errors.

2. Replace the Outlet high limit.

3. If previous steps are correct and fault persists,

replace the module.

H or L

80

DHW high limit

1. Check wiring and correct any possible errors.

2. Replace the DHW high limit.

3. If previous steps are correct and fault persists,

replace the module.

H or L

81

Delta T limit

1. Check Inlet and Outlet sensors and pump circuits

for proper operation.

2. Recheck the Delta T Limit to confirm proper

setting.

3. If previous steps are correct and fault persists,

replace the module.

H or L

82

Stack limit

1. Check wiring and correct any possible errors.

2. Replace the Stack high limit.

3. If previous steps are correct and fault persists,

replace the module.

H or L

83

Delta T exchanger/outlet limit

Not Applicable.

H or L

84

Delta T inlet/exchanger limit

Not Applicable.

H or L

85

Inlet/outlet inversion limit

Not Applicable.

H or L

86

Exchanger/outlet inversion limit

Not Applicable.

H or L

87

Inlet/exchanger inversion limit

Not Applicable.

H or L

88

Outlet T-rise limit

Check for adequate flow.

H or L

89

Exchanger T-rise limit

Not Applicable.

H or L

90

Heat exchanger high limit

Not Applicable.

H or L

Sensor Faults

91

Inlet sensor fault

1. Check wiring and correct any possible errors.

2. Replace the Inlet sensor.

3. If previous steps are correct and fault persists,

replace the module.

H

92

Outlet sensor fault

1. Check wiring and correct any possible errors.

2. Replace the Outlet sensor.

3. If previous steps are correct and fault persists,

replace the module.

H

93

DHW sensor fault

1. Check wiring and correct any possible errors.

2. Replace the DHW sensor.

3. If previous steps are correct and fault persists,

replace the module.

H