CODE

DESCRIPTION

RECOMMENDED TROUBLESHOOTING OF

LOCKOUT CODES

NOTE

212

Invalid Preignition time setting

1. Return to Configuration mode and recheck

selected parameters, reverify and reset module.

2. If fault repeats, verify electrical grounding.

3. If fault repeats, replace module.

L

213

Invalid Prepurge rate setting

L

214

Invalid Prepurge time setting

L

215

Invalid Purge rate proving setting

L

216

Invalid Run flame failure response setting

L

217

Invalid Run stabilization time setting

L

218

Invalid Stack limit enable setting

L

219

Invalid Stack limit response setting

L

220

Unconfigured Delta T limit setpoint setting

L

221

Unconfigured DHW high limit setpoint setting

L

222

Unconfigured Outlet high limit setpoint setting

L

223

Unconfigured Stack limit setpoint setting

L

224

Invalid DHW demand source setting

L

225

Invalid Flame threshold setting

L

226

Invalid Outlet high limit setpoint setting

L

227

Invalid DHW high limit setpoint setting

L

228

Invalid Stack limit setpoint setting

L

229

Invalid Modulation output setting

L

230

Invalid CH demand source setting

L

231

Invalid Delta T limit delay setting

L

232

Invalid Pressure sensor type setting

L

233

Invalid IAS closed response setting

L

234

Invalid Outlet high limit enable setting

Contact the qualified service technician.

L

235

Invalid Outlet connector type setting

Contact the qualified service technician.

L

236

Invalid Inlet connector type setting

Contact the qualified service technician.

L

237

Invalid DHW connector type setting

Contact the qualified service technician.

L

238

Invalid Stack connector type setting

Contact the qualified service technician.

L

239

Invalid S2 (J8-6) connector type setting

Contact the qualified service technician.

L

240

Invalid S5 (J8-11) connector type setting

Contact the qualified service technician.

L

241

Exchanger sensor not allowed with stack

connector setting

Not Applicable.

L

242

Invalid DHW auto detect configuration

Not Applicable.

L

243

Invalid UV with spark interference not compatible

with Igniter on throughout PFEP

Contact the qualified service technician.

L

244

Internal fault: Safety relay test invalid state

Contact the qualified service technician.

L

245

Invalid Outlet connector type setting for Trise

Contact the qualified service technician.

L

246

4-20mA cannot be used for both modulation and

setpoint control

Contact the qualified service technician.

L

247

Invalid ILK bounce detection enable

Not Applicable.

L

248

Invalid forced recycle interval

Not Applicable.

L

249

STAT cannot be demand source when Remote

Stat is enabled

Not Applicable.

L

250

Invalid Fan speed error response

1. Check fan cables secured properly. If fault

persists contact the qualified service technician.

L

251-255 RESERVED