CODE

DESCRIPTION

RECOMMENDED TROUBLESHOOTING OF

LOCKOUT CODES

NOTE

122

Lightoff rate proving failed

1. Check wiring and correct any potential wiring

errors.

2. Check VFDs ability to change speeds.

3. Change the VFD

4. If the fault persists, replace the module.

L

123

Purge rate proving failed

L

124

High fire switch OFF

1. Check wiring and correct any potential wiring

errors.

2. Check High Fire Switch to assure proper function

(not welded or jumpered).

3. Manually drive the motor to the High Fire position

and adjust the HF switch while in this position

and verify voltage through the switch to the HFS

input with a voltmeter.

4. If steps 1-3 are correct and the fault persists,

replace the module.

H

125

High fire switch stuck ON

H

126

Low fire switch OFF

1. Check wiring and correct any potential wiring

errors.

2. Check Low Fire Switch to assure proper function

(not welded or jumpered).

3. Manually drive the motor to the High Fire position

and adjust the LF switch while in this position and

verify voltage through the switch to the LFS input

with a voltmeter.

4. If steps 1-3 are correct and the fault persists,

replace the module.

H

127

Low fire switch stuck ON

H or L

128

Fan speed failed during prepurge

1. Check wiring and correct any potential wiring

errors.

2. Check VFDs ability to change speeds.

3. Change the VFD

4. If the fault persists, replace the module.

H or L

129

Fan speed failed during preignition

H or L

130

Fan speed failed during ignition

H or L

131

Fan movement detected during standby

H

132

Fan speed failed during run

H

133-135 RESERVED

Start Check Faults

136

Interrupted Airflow Switch failed to close

1. Check wiring and correct any possible wiring

errors.

2. Check Interrupted Airflow switch(es) to assure

proper function.

3. Verify voltage through the airflow switch to the

IAS input with a voltmeter.

4. If steps 1-3 are correct and the fault persists,

replace the module.

H

137

ILK failed to close

1. Check wiring and correct any possible shorts.

2. Check Interlock (ILK) switches to assure proper

function.

3. Verify voltage through the interlock string to the

interlock input with a voltmeter.

4. If steps 1-3 are correct and the fault persists,

replace the module.

H

138-142 RESERVED

FAULT CODES 149 THROUGH 165 ARE

OEM SPECIFIC FAULT CODES.

143

Internal fault: Flame bias out of range 1

Contact the qualified service technician.

L

144

Internal fault: Flame bias out of range 2

Contact the qualified service technician.

L

145

Internal fault: Flame bias out of range 3

Contact the qualified service technician.

L

146

Internal fault: Flame bias out of range 4

Contact the qualified service technician.

L

147

Internal fault: Flame bias out of range 5

Contact the qualified service technician.

L

148

Internal fault: Flame bias out of range 6

Contact the qualified service technician.

L