ALL VENT PIPE MATERIALS AND FITTINGS MUST COMPLY WITH THE FOLLOWING:

ITEM

MATERIAL

STANDARDS FOR INSTALLATION IN:

UNITED STATES

CANADA

Vent pipe and fittings

PVC schedule 40

ANSI/ASTM D1785 PVC, CPVC and Polypropylene venting must be

ULC-S636 Certified.

CPVC schedule 40/80

ANSI/ASTM F441

Polypropylene

UL 1738

Pipe cement/primer

PVC

ANSI/ASTM D2564 ULC-S636 Certified.

CPVC

ANSI/ASTM F493

NOTICE: DO NOT USE CELLULAR (FOAM) CORE PIPE

TABLE 12. PVC, VENT PIPE, AND FITTINGS

TABLE 13. DIRECT VENT ALLOWABLE AIR/VENT LENGTHS

MODELS

(XB)

AIR INTAKE

DIAMETER

(INCH)

AIR INTAKE

MIN. LENGTH

FEET (M)

AIR INTAKE

MAX. LENGTH

FEET (M)

VENT

DIAMETER

(INCH)

VENT MIN.

LENGTH

FEET (M)

VENT MAX.

LENGTH

FEET (M)

1000

6

12 (3.7)

100 (30.5)

6

10 (3)

100 (30.5)

1300

6

12 (3.7)

100 (30.5)

8

10 (3)

100 (30.5)

1700

8

12 (3.7)

100 (30.5)

8

10 (3)

100 (30.5)

2000

8

12 (3.7)

100 (30.5)

8

10 (3)

100 (30.5)

2600

8

12 (3.7)

100 (30.5)

8

10 (3)

100 (30.5)

3400

10

12 (3.7)

100 (30.5)

10

10 (3)

100 (30.5)

TABLE 14. ROOM AIR ALLOWABLE VENT LENGTHS

MODELS

(XB)

VENT DIAMETER

(INCH)

VENT MIN. LENGTH

FEET (M)

VENT MAX. LENGTH

FEET (M)

1000

6

10 (3)

100 (30.5)

1300

8

10 (3)

100 (30.5)

1700

8

10 (3)

100 (30.5)

2000

8

10 (3)

100 (30.5)

2600

8

10 (3)

100 (30.5)

3400

10

10 (3)

100 (30.5)

NOTE: When determining equivalent combustion air and vent length, add 10 feet (3 m) for each 90° elbow and 5 feet (1.5 m) for each

45° elbow. The Vent Max. Length does not include appliance elbows and adapters shipped with the unit.

VENT

MATERIAL

START-BASE VENT

FIELD VENT LENGTHS &

FITTINGS

TERMINATIONS &

RAIN CAPS

INTAKE

EXHAUST

INTAKE

EXHAUST

INTAKE

EXHAUST

Polypropylene

Venting

Air Intake

Box (Adapter

required to install

Polypropylene

pipes, can

use Adapter

discarded from

exhaust).

Use

Polypropylene

Kit shipped with

the unit, Discard

PVC/CPVC

Adapter or use

it with Air Intake

for Direct Vent

applications.

Use

Polypropylene

pipes and

fittings.

Use

Polypropylene

pipes and

fittings.

Polypropylene

90° elbows.

Polypropylene

Tee.

PVC/CPVC

Venting

Air Intake Box

will readily fit

the PVC/CPVC

pipes.

Use both

Polypropylene

Kit + PVC/CPVC

Adapter (shipped

with the unit).

Use PVC/

CPVC pipes and

fittings.

Use PVC/

CPVC pipes

and fittings.

PVC 90° elbows

with wire mesh.

PVC Tee with

wire mesh/ Rain

Caps.

Stainless Steel

Venting

Adapter required

to fit to the Air

Intake Box.

Pre-order unit

with Stainless

Steel Factory Kit.

Use Stainless

Steel pipes and

fittings.

Use Stainless

Steel pipes

and fittings.

Adapter required

+ PVC 90°

elbows with wire

mesh.

Adapter required

+ PVC Tee with

wire mesh/ Rain

Caps.

TABLE 15. COMPLETE VENTING SYSTEM