FLOW, HEAD AND TEMPERATURE RISE

TABLE 6. XB MODELS - FLOW, HEAD AND TEMPERATURE RISE

Models

Input

(Btu/hr)

Output

(Btu/hr)

Water

Flow

Temperature Rise - ΔT °F

Flow Rate

20

30

40

Maximum

Minimum

XB-1000

920,000

855,600

GPM

86

56

43

86

43

LPM

325

211

162

325

162

ΔP FT

26

12

7

26

7

ΔP M

7.9

3.7

2.1

7.9

2.1

XB-1300

1,300,000

1,209,000

GPM

120

80

60

120

60

LPM

453

302

226

453

226

ΔP FT

32.5

15

8

32.5

8

ΔP M

9.9

4.6

2.4

9.9

2.4

XB-1700

1,700,000

1,581,000

GPM

156

104

78

156

78

LPM

592

395

296

592

296

ΔP FT

35

14

8

35

8

ΔP M

10.7

4.3

2.4

10.7

2.4

XB-2000

1,999,900

1,860,000

GPM

184

123

92

184

92

LPM

696

464

348

696

348

ΔP FT

26

12

7

26

7

ΔP M

7.9

3.7

2.1

7.9

2.1

XB-2600

2,600,000

2,418,000

GPM

239

159

120

239

120

LPM

905

604

453

905

453

ΔP FT

32.5

15

8

32.5

8

ΔP M

9.9

4.6

2.4

9.9

2.4

XB-3400

3,400,000

3,162,000

GPM

313

209

156

313

156

LPM

1184

789

592

1184

592

ΔP FT

35

14

8

35

8

ΔP M

10.7

4.3

2.4

10.7

2.4

NOTE: Head Loss shown is through the boiler only and allows for no additional piping.