PIPE SIZES FOR PROPANE GAS

Make sure to contact the gas supplier for pipe sizes, tanks, and

100% lockup gas pressure regulator.

PURGING GAS LINE

Gas line purging is required with new piping or systems in which

air has entered. Gas purging should be performed per NFPA 54

for US and CAN B149.1 for Canada.

CHECK GAS SUPPLY INLET PRESSURE

CSA or UL listed flexible gas connections are acceptable, but

make sure that the line has adequate capacity to allow your boiler

to fire at full rate. Consult with local codes for proper installation

or service procedures.
Do not adjust or attempt to measure gas control valve outlet

pressure. Attempting to alter or measure the gas control valve

outlet pressure could result in damage to the valve, causing

potential severe personal injury, death, or substantial property

damage.
Make sure the gas piping are sized for the proper flow and length

of pipe, to avoid excessive pressure drop. The gas meter and

the gas regulator must be properly sized for the total gas load.
Perform the below steps when checking inlet gas supply:
1. Turn the main power switch to the “OFF” position.
2. Shut off gas supply.
3. Remove the 1/8" pipe plug on the main gas shutoff valve

and install a suitable 1/8" fitting (field supplied) for the

manometer tubing. Place the tubing of the manometer over

the tap once the 1/8" fitting is installed.

4. Slowly turn on the gas supply.
5. Ensure inlet pressure is within specified range.
6. If the gas pressure is out of range, contact the gas utility, gas

supplier, qualified installer or service agency to determine

the necessary steps to provide proper gas pressure to the

control.

CHECK FOR GAS LEAKS

Before operating the boiler, make sure to check the floor near and

around the boiler for gas odorant or any unusual odor. Remove

the top access panel and check for odor in the interior of the

boiler enclosure. Do not start the boiler if there is any indication

of a gas leak. Use an approved leak detection solution and repair

any leaks at once.
In the case of propane boilers, the supplier mixes an odorant

with the propane to make its presence detectable. But in some

instances, the odorant can fade, and the gas may no longer have

an odor. Before operating the boiler, make sure the propane

supplier verify the correct odorant level in the gas.
Do not adjust or attempt to measure gas control valve outlet

pressure. The gas control valve is factory set for the correct

outlet pressure. This setting is suitable for natural gas and

propane, requiring no field adjustment. Attempting to alter or

measure the gas control valve outlet pressure could result in

damage to the valve, causing potential severe personal injury,

death, or substantial property damage.