beautypg.com

Venting maintenance, Heat exchanger maintenance, Venting maintenance heat exchanger maintenance – A.O. Smith 3400 User Manual

Page 76

background image

76

1. Turn off the electrical power, and manual gas shut-off.

Allow boiler parts to cool before disassembly.

2. Remove the vent pipe.

Check parts and chimney for obstructions and clean as

necessary.

3. Remove burner from boiler and other metal parts as required

to clean as necessary.

Refer to parts list for disassembly aid.

4. Clean and reinstall the parts removed in steps 2 and 3.

Be sure the vent pipe has a minimum upward pitch of 1/4"

per foot (2 cm/m) of length and is sealed as necessary.

5. Restore electrical power and gas supply to boiler.

Check for gas leaks and proper boiler and vent operation.

HEAT EXCHANGER MAINTENANCE

1. Shut down the boiler:

• Turn Off gas to the boiler.
• Do not drain the boiler unless it will be exposed to

freezing temperatures. If using freeze prevention fluid in

system, do not drain.

2. Ensure the boiler cools down to room temperature.
3. Remove the nuts securing the heat exchanger access cover

to the heat exchanger and set aside.

4. Remove the heat exchanger access cover, burner, and gas

train assembly.

NOTE: The boiler contains ceramic fiber materials. Failure to

comply could result in severe personal injury.
5. Remove the condensate hose from the heat exchanger end.

Connect a field supplied 3/4" diameter hose to a drain pan.

6. Use a vacuum cleaner to remove any deposits/ debris on the

boiler heating surfaces. Do not use any solvent.

7. Brush the heat exchanger while dry using a nylon bristle

brush. Re-vacuum the heat exchanger.

8. Finish cleaning using a clean cloth dampened with warm

water. Rinse out debris with a low pressure water supply.

9. Allow the heat exchanger to dry completely.
10. Remove the rear refractory cover from the back of the

combustion chamber of the heat exchanger and reassemble.

11. Close isolation valves on piping to isolate the boiler from

system. Attach a hose to the boiler drain and flush boiler

thoroughly with clean water by using purging valves to allow

water to flow through the water make-up line to the boiler.

12. Replace the access cover and restore the boiler for operation.

CONDENSATE REMOVAL SYSTEM

Due to the highly efficient operation of this unit, condensate is

formed during operation and must be removed by the conden-

sate drain systems. Inspect the condensate drains and tubes

at least once a month and insure they will allow the free flow

of condensate at all times. The system must be inspected

more frequently in cold weather if the drain system is located

in an area, such as along the floor, where freezing tempera-

tures are likely to occur. The conden sate drain system must

be protected against freezing. Contact a qualified service

technician to inspect and correct the condition if freezing of

the conden sate lines is a problem.
The transparent drain lines and condensate drain on the bottom

of the vent collector should be visually inspected at one month

intervals for blockage, particularly in the areas of the loops in the

lines which trap a small amount of conden sate, and the exit point

of the vent collector drain. Conden sate in portions of the line

other than the loop area indicates a blockage in the drain line.

Flush the lines with air or water and clear or replace the blocked

portions of the line as necessary. Note that areas of the drain

line which include a sag or low spot in the line will also form a

condensate trap which can be removed by levelling the tube and

does not indicate a blocked system.
Inspect the metal vent drain and vent collector drain connectors

at six month inter vals. Remove the hoses from the connections,

then check with a small wooden dowel or plastic rod passed

up through the metal con nection to insure the passage is clear,

using caution to not bend or damage the connector. Call a

qualified service technician to inspect and correct the problem

if any obstructions are found in the connectors. Replace all

hoses and clamps immediately after inspec tion and before

starting the boiler in accordance with the Lighting and Operating

Instructions. Do not operate the boiler unless all condensate

drain lines are properly connected and working

. When a means

to neutralize condensate has been installed you must also follow

operating, inspection and maintenance procedures specified by

the manufacturer of the product. Inspect the installed device to

insure that it does not cause condensate to remain in the boiler

or vent for any reason.

VENTING MAINTENANCE

It is recommended that the intake and exhaust piping of the

boiler be checked every 6 months for dust, condensate leakage,

deterioration and carbon deposits.

Qualified service technician should follow this procedure when the

boiler’s intake and exhaust piping need cleaning:

This manual is related to the following products: