beautypg.com

A.O. Smith 3400 User Manual

Page 35

background image

35

DIRECT VENT: HORIZONTAL TERMINATION

Gas vent extending through an exterior wall must not terminate

adjacent to a wall or below building extensions such as eaves,

parapets, balconies, or decks. Failure to comply could result in

severe personal injury, death, or substantial property damage.
Installation must comply with local requirements and with the

National Fuel Gas Code, ANSI Z223.1 for U.S. installations or

CSA B149.1 for Canadian installations.
VENT/AIR TERMINATION LOCATIONS:
Follow these guidelines for locating the vent/air terminations:
1. Make sure the total length of piping for vent or air do not

exceed the limits mentioned in Table 13 and Table 14 on

Page 37.

2. Consider the surroundings when terminating the vent and

air:
• While positioning the vent termination, ensure vapors

will not damage nearby shrubs, plants or air conditioning

equipment.

• The flue products will form a noticeable plume as they

condense in cold air. Avoid areas where the plume could

obstruct window views.

• Prevailing winds could cause freezing of condensate

and water/ice buildup where flue products impinge on

building surfaces or plants.

• Do not allow accidental contact of flue products with

people or pets.

• Do not locate the terminations near building corners,

near adjacent buildings or surfaces, window wells,

stairwells, alcoves, courtyards, or other recessed areas,

where wind eddies could affect performance or cause

recirculation .

• Sidewall vent and air inlet terminations must terminate in

the same pressure zone.

• Do not terminate above any door or window, where

condensate can freeze, causing ice formations.

• Locate or monitor the vent to prevent condensate

damage to exterior finishes.

3. The air piping must terminate in a down-turned elbow, using

a mesh screen. This setup will avoid recirculation of flue

products into the combustion air stream. See Figure 32.

4. The vent piping must terminate with a Tee pointed upwards

and away from the air inlet. See Figure 32.

5. Maintain clearances as shown in Figure 32 and Figure 33.

Vent must terminate:

• At least 6 feet (1.8 m) from adjacent walls.
• No closer than 12 inches (305 mm) below roof overhang.
• At least 7 feet (2.1 m) above any public walkway.
• At least 3 feet (0.9 m) above any forced air intake within

10 feet (3 m).

• No closer than 12 inches (305 mm) below or horizontally

from any door or window or any other gravity air inlet.

Air inlet must terminate at least 12 inches (305 m) above grade or

snow line; at least 12 inches (305 mm) below the vent termination;

and the vent pipe must not extend more than 24 inches (610 mm)

vertically outside the building as shown in Figure 32 and Figure

33.

Do not terminate closer than 4 feet (1.2 m) horizontally from

any electric meter, gas meter, regulator, relief valve, or other

equipment. Never terminate above or below any of these within

4 feet (1.2 m) horizontally.
6. Locate terminations so they are not likely to be damaged by

foreign objects, such as stones or balls, or subject to buildup

of leaves or sediment.

FIGURE 32. AIR/VENT TERMINATION - HORIZONTAL

FIGURE 33. HORIZONTAL CLEARANCES - AIR/VENT

TERMINATION

This manual is related to the following products: