The trigger starts the measurement. First choose the

source of trigger

. Trigger sources can be

measurement values, digital inputs, status of inverter, etc. The starting conditions are defined
by

trigger level

resp.

trigger edge

.

ATTENTION

The increments of the trigger levels are different depending on the trigger source. Therefore
not every value can be set. After starting a recording, the closest possible values is calculated
and set.

Time between two measured values is set by

sampling rate

. Numbers of

measured value

s and

sampling rate define the

time of sampling

.

The

Pre-trigger/Delay

set the beginning of the measurement in relation to the trigger event.

Note:

The dynamic of measured values defines the best rate of sampling: fast changing values need
a low sampling rate. The number of measured values defines the time of sending the values
from inverter to

NORD CON

.

3. Sampling modes

The oscilloscope has 2 differently modes. The user can choose between "Single" and "Roll"
mode. The "Single" mode is the standard mode. In this mode starts a recording with the current