Technical data – KROHNE IFC 050 Converter EN User Manual

Page 76

background image

8

TECHNICAL DATA

76

IFC 050

www.krohne.com

08/2013 - 4002184002 - MA IFC 050 R02 en

Pulse or frequency output

Pulse or frequency output

Pulse or frequency output

Pulse or frequency output

Output data

Flow

Function

Can be set as a pulse output or frequency output

Pulse rate/frequency

0.01...10000 pulses/s or Hz

Settings

Pulses per volume or mass unit or max. frequency for 100% flow

Pulse width: adjustable as automatic, symmetric or fixed (0.05...500 ms)

Operating data

Operating data

Operating data

Operating data

Basic I/Os + Modbus

Basic I/Os + Modbus

Basic I/Os + Modbus

Basic I/Os + Modbus

Active

This output is intended to drive mechanical or electronic counters directly.

U

int, nom

≤ 20 V

R

V

= 1 kΩ

C = 1000 µF

High current mechanical counter

High current mechanical counter

High current mechanical counter

High current mechanical counter

f

max

≤ 1 Hz

Low current mechanical counter

Low current mechanical counter

Low current mechanical counter

Low current mechanical counter

I ≤ 20 mA

R

L

≤ 10 kΩ for f ≤ 1 kHz

R

L

≤ 1 kΩ for f ≤ 10 kHz

closed:

U

0

≥ 12.5 V at I = 10 mA

open:

I ≤ 0.05 mA at U

nom

= 20 V

Passive

Independent of connection polarity.

U

ext

≤ 32 VDC

f

max

in operating menu set to

f

max

≤ 100 Hz:

I ≤ 100 mA

open:

I ≤ 0.05 mA at U

ext

= 32 VDC

closed:

U

0, max

= 0.2 V at I ≤ 10 mA

U

0, max

= 2 V at I ≤ 100 mA

f

max

in operating menu set to

100 Hz < f

max

≤ 10 kHz:

I ≤ 20 mA

open:

I ≤ 0.05 mA at U

ext

= 32 VDC

closed:

U

0, max

= 1.5 V at I ≤ 1 mA

U

0, max

= 2.5 V at I ≤ 10 mA

U

0, max

= 5.0 V at I ≤ 20 mA