ELECTRICAL CONNECTIONS

42

IFC 050

www.krohne.com

08/2013 - 4002184002 - MA IFC 050 R02 en

4.11.4 HART

®

connection

Example for active HART

®

connection (point-to-point)

The parallel resistance to the HART

®

communicator must be R ≥ 230 Ω.

Example for passive HART

®

connection (multi-drop mode)

• I: I

0%

≥ 4 mA

• Multi-drop mode I: I

fix

≥ 4 mA = I

0%

• U

ext

≤ 32 VDC

• R ≥ 230 Ω

INFORMATION!
The current output always has HART

®

capability and is connected at connection terminals A+/A-

/A.
All HART

®

connections (point-to-point and multi-drop operation) both work actively and

passively.