ELECTRICAL CONNECTIONS

4

23

IFC 050

www.krohne.com

08/2013 - 4002184002 - MA IFC 050 R02 en

4.4.4 Preparing field current cable C, connection to signal converter

• Field current cable C is not part of the scope of delivery.
• Bending radius: ≥ 50 mm / 2"

Required materials:

• Shielded, at least 2-wire copper cable with suitable heat-shrinkable tubing
• Insulating tube, size according to the cable being used
• Wire end ferrules to DIN 46 228: size according to the cable being used

Length and cross-section of field current cable C

DANGER!
A shielded 2-wire copper cable is used as the field current cable. The shielding MUST

MUST

MUST

MUST be

connected in the housing of the measuring sensor and signal converter.

INFORMATION!
Assembly materials and tools are not part of the delivery. Use the assembly materials and tools
in compliance with the applicable occupational health and safety directives.

Length

Cross-section A

F

(Cu)

[m]

[ft]

[mm

2

]

[AWG]

0...150

0...492

2 x 0.75 Cu

1

2 x 18

150...300

492...984

2 x 1.5 Cu

1

2 x 14

300...600

984...1968

2 x 2.5 Cu

1

2 x 12

1 Cu = copper cross-section