ELECTRICAL CONNECTIONS

4

39

IFC 050

www.krohne.com

08/2013 - 4002184002 - MA IFC 050 R02 en

Pulse/frequency output passive

• U

ext

≤ 32 VDC

• f

max

in the operating menu set to f

max

≤ 100 Hz:

I ≤ 100 mA
R

L

≤ 47 kΩ

closed:
U

0

≤ 0.2 V at I = 10 mA

U

0

≤ 2 V at I = 100 mA

open:
I ≤ 0.05 mA at U

ext

= 32 V

• f

max

in operating menu set to 100 Hz < f

max

≤ 10 kHz:

(over range up to f

max

≤ 12 kHz)

I ≤ 20 mA
R

L

≤ 10 kΩ for f ≤ 1 kHz

R

L

≤ 1 kΩ for f ≤ 10 kHz

closed:
U

0

≤ 1.5 V at I = 1 mA

U

0

≤ 2.5 V at I = 10 mA

U

0

≤ 5 V at I = 20 mA

open:
I ≤ 0.05 mA at U

ext

= 32 V

Use shielded cables!

• The minimum load impedance R

L, min

is calculated as follows:

R

L, min

= (U

ext

- U

0

) / I

max

• Can also be set as status output; for the electrical connection refer to status output

connection diagram.

INFORMATION!

For frequencies above 100 Hz, shielded cables are to be used in order to reduce effects from
electrical interferences (EMC).

Shielding takes place at the electrical connection (S) of the output terminal block.

INFORMATION!

Independent of connection polarity.

The output is open if the signal converter is not powered.

Figure 4-15: Pulse/frequency output passive P