Operation – KROHNE IFC 050 Converter EN User Manual
Page 55
OPERATION
6
55
IFC 050
www.krohne.com
08/2013 - 4002184002 - MA IFC 050 R02 en
C1.4 information
C1.4.1
liner
Shows material of the liner
C1.4.2
electr. material
Shows material of the electrodes.
C1.4.3
calibration date
Date on which the measuring sensor was calibrated
C1.4.4
serial no. sensor
Shows serial no. of the measuring sensor
C1.4.5
V no. sensor
Shows the order number of the measuring sensor
C1.4.6
sensor electr. info
Shows serial number of circuit board, software version number and
calibration date of circuit board
C1.5 simulation
C1.5.2
volume flow
mass flow
Sequence see Fct. B1.1
No.
Function
Settings / descriptions
C2 I/O (Inputs/Outputs)
C2.1 hardware
C2.1.1
terminal A
Select:
off (switched off) / current output
C2.1.2
terminal D
Select:
off (switched off) / frequency output / pulse output / status output / limit
switch
C2.2 current output A
C2.2.1
range 0%…100%
Current range for the selected "measurement", e.g. 4...20 mA,
corresponds to 0…100%
xx.x … xx.x mA;
range: 0.00…20 mA (condition: 0 mA ≤ 1st value ≤ 2nd value ≤ 20 mA)
C2.2.2
extended range
Min. and max. limits of current values. If the current range is exceeded, the
current is set to these limits.
xx.x…xx.x mA; range: 03.5…21.5 mA (condition: 0 mA ≤ 1st value ≤ 2nd value
≤ 21.5 mA and out of current range)
C2.2.3
error current
Specify error current
xx.x mA; range: 3…22 mA (condition: outside of extended range)
C2.2.4
error condition
The following error conditions can be selected:
Select:
error in device (error category [F]) /
application error (error category [F]) /
out of specification (error category [F] & [S])
C2.2.5
polarity
Set polarity, please note flow direction in C1.2.2!
Select:
both polarities (plus and minus values are displayed) /
positive polarity (display for negative values = 0) /
negative polarity (display for positive values = 0) /
absolute value (always displays positive, with both negative and positive
values)
C2.2.6
low flow cutoff
Sets the measurement to "0" for low values
x.xxx ± x.xxx%; range: 0.0…20%
(1st value = switching point / 2nd value = hysteresis),
condition: 2nd value ≤ 1st value