OPERATION

6

55

IFC 050

www.krohne.com

08/2013 - 4002184002 - MA IFC 050 R02 en

C1.4 information

C1.4.1

liner

Shows material of the liner

C1.4.2

electr. material

Shows material of the electrodes.

C1.4.3

calibration date

Date on which the measuring sensor was calibrated

C1.4.4

serial no. sensor

Shows serial no. of the measuring sensor

C1.4.5

V no. sensor

Shows the order number of the measuring sensor

C1.4.6

sensor electr. info

Shows serial number of circuit board, software version number and

calibration date of circuit board

C1.5 simulation

C1.5.2

volume flow

mass flow

Sequence see Fct. B1.1

No.

Function

Settings / descriptions

C2 I/O (Inputs/Outputs)

C2.1 hardware

C2.1.1

terminal A

Select:

off (switched off) / current output

C2.1.2

terminal D

Select:

off (switched off) / frequency output / pulse output / status output / limit

switch

C2.2 current output A

C2.2.1

range 0%…100%

Current range for the selected "measurement", e.g. 4...20 mA,

corresponds to 0…100%

xx.x … xx.x mA;

range: 0.00…20 mA (condition: 0 mA ≤ 1st value ≤ 2nd value ≤ 20 mA)

C2.2.2

extended range

Min. and max. limits of current values. If the current range is exceeded, the

current is set to these limits.

xx.x…xx.x mA; range: 03.5…21.5 mA (condition: 0 mA ≤ 1st value ≤ 2nd value

≤ 21.5 mA and out of current range)

C2.2.3

error current

Specify error current

xx.x mA; range: 3…22 mA (condition: outside of extended range)

C2.2.4

error condition

The following error conditions can be selected:

Select:

error in device (error category [F]) /

application error (error category [F]) /

out of specification (error category [F] & [S])

C2.2.5

polarity

Set polarity, please note flow direction in C1.2.2!

Select:

both polarities (plus and minus values are displayed) /

positive polarity (display for negative values = 0) /

negative polarity (display for positive values = 0) /

absolute value (always displays positive, with both negative and positive

values)

C2.2.6

low flow cutoff

Sets the measurement to "0" for low values

x.xxx ± x.xxx%; range: 0.0…20%

(1st value = switching point / 2nd value = hysteresis),

condition: 2nd value ≤ 1st value