Installation for energy measurement, 2 program the process input – KROHNE OPTISONIC 6300 P-6400 EN User Manual
Page 39
INSTALLATION FOR ENERGY MEASUREMENT
4
39
OPTISONIC 6300 P
www.krohne.com
03/2013 - 4000972603 - MA OPTISONIC 6300 P R03 en
If another energy set is used, teach in the required values.
4.3.2 Program the process input
• Go to menu 2.4.2.3.1 via "Measurement Setup Process input Heat Function off "
• Choose "Heating" or "Cooling" to activate energy measurement.
• Choose in "Temperature input " which sensor is is located at the supply side of the process.
2.4.5.2
Function
Function
Function
Function
Extended range A 0%
Extended range A 100%
Extended range B 0%
Extended range B 100%
Temperature range A 0%
Temperature range A 100%
Temperature range B 0%
Temperature range B 100%
Time constant A
Time constant B
4 mA trimming A
20 mA trimming A
4 mA trimming B
20 mA trimming B
On
On
On
On
3.6 mA
21 mA
3.6 mA
21 mA
0.0 °C
120.0 °C
0.0 °C
120.0 °C
1 s
1 s
4 mA
20 mA
4 mA
20 mA
13-04-2010 14:11:09 13 MB free
INFORMATION!
The "Extended range A/B 0% and 100%" are meant for an alarm function. If a value is measured
that is lower than the "Extended range A/B 0%" value or higher than the "Extended range A/B
100%" value, an event will be logged in the event logger.
2.4.2.3.1
Heating
Heating
Heating
Heating
Cooling
Off
13-04-2010 14:11:09 13 MB free
2.4.2.3
Function
Temperature input
Temperature input
Temperature input
Temperature input
Sensor location
Fluid
Heating
Terminal A at supply
Terminal A at supply
Terminal A at supply
Terminal A at supply
Supply
Water
13-04-2010 14:11:09 13 MB free
INFORMATION!
In case the function is "Heating", the temperature at the "supply" side is the highest.
In case the function is "Cooling", the temperature at the "supply" side is the lowest.