INSTALLATION FOR FLOW MEASUREMENT

3

15

OPTISONIC 6300 P

www.krohne.com

03/2013 - 4000972603 - MA OPTISONIC 6300 P R03 en

Open feed or discharge

Install meter on a lowered section of the pipe to make sure that there is a full pipe condition.

Down going pipeline over 5 m / 16 ft length

Install an air vent downstream of the flowmeter to prevent vacuum. It may cause gases to come
out of solution (cavitate) that prevent a proper measurement.

Position of control valve

Always install control valves downstream of the flowmeter in order to avoid cavitation or
distortion of the flow profile.

Figure 3-4: Open feed or discharge

Figure 3-5: Down going pipeline over 5 m / 16 ft length

Figure 3-6: Position of control valve