Power state definitions
TABLE 14
Power state Definition
Idle
All ports down, no optics or cables connected.
Typical
56x10 GbE, 4x40 GbE, and 4x4x10 GbE ports linked and up. 10% traffic with 64-byte packets. Fans
at normal speed.
Maximum
All ports connected with optics to draw maximum power per MSA Optics Specification. Traffic at full
rate or 100% throughput. Fans at full speed.
The following table lists the power supply specifications for the AC power draw for the Brocade ICX
6650.
AC power supply system power specifications
TABLE 15
AC voltage
Input watts
BTU/hr
Power state
100-120 VAC
114.6
391.14
Idle
100-120 VAC
154.6
527.66
Typical Light Load
100-120 VAC
171.6
585.68
Typical Full Load
100-120 VAC
230
785.01
Maximum
Inrush current should be limited to a 35A peak for any initial current surge or spike of 10 ms or less at
either cold or warm start. Any additional inrush current surges or spikes in the form of AC cycles or
multiple AC cycles greater than 10 ms and less than 150 ms must not exceed a 25A peak. After 150
ms, the AC input current will be less than the rating of input fuses and the other components within the
power supply.
The following table lists the power supply specifications for the DC power draw for the Brocade ICX
6650.
DC power supply system power specifications
TABLE 16
DC voltage
Input watts
BTU/hr
Power state
40-60 VDC
114.6
391.14
Idle
40-60 VDC
154.6
527.66
Typical Light Load
40-60 VDC
171.6
585.68
Typical Full Load
40-60 VDC
230
785.01
Maximum
Brocade ICX 6650 Specifications