Installation and safety considerations, Electrical considerations, Environmental considerations – Brocade ICX 6650 Hardware Installation Guide User Manual
Page 24: Location considerations

‐
Two mounting ears and screws
‐
Grounding terminal screw
•
Installed filler panels for the right power supply unit (PSU1) slot and left fan slot.
CAUTION
The filler panels must be in place if operating the switch with only one power supply and fan.
Installation and safety considerations
You can install the Brocade ICX 6650 in the following ways:
•
As a standalone unit on a flat surface.
•
In an EIA cabinet using a fixed-rail rack mount kit. The optional fixed-rail rack mount kit can be
ordered from your switch retailer. Both the 24"-28" rack depth kit and the 28"-32" rack depth kit
will work with the Brocade ICX 6650.
•
In a 2-post Telco rack using a flush mount rack kit. The optional flush mount rack kit for switches
can be ordered from your switch retailer.
•
In a 2-post Telco rack using a mid-mount rack kit. The optional mid-mount rack kit for switches
can be ordered from your switch retailer.
Electrical considerations
To install and operate the switch successfully, ensure compliance with the following requirements:
•
The primary outlet is correctly wired, protected by a circuit breaker, and grounded in accordance
with local electrical codes.
•
The supply circuit, line fusing, and wire size are adequate, as specified by the electrical rating on
the switch nameplate.
•
The power supply standards are met.
Environmental considerations
For successful installation and operation of the switch, ensure that the following environmental
requirements are met:
•
Because the Brocade ICX 6650 can be ordered with fans that move air either front to back or
back to front, be sure to orient your switch with the airflow pattern of any other devices in the rack.
All equipment in the rack should force air in the same direction to avoid intake of exhaust air.
•
The ambient air temperature does not exceed 40° C (104° F) while the switch is operating.
•
Some combinations of intake and exhaust airflows may not be compatible with your environment.
Consult your fan and power supply module FRU kit to determine the correct configuration.
Location considerations
Before installing the device, plan its location and orientation relative to other devices and equipment.
Devices can be mounted in a standard 19-inch equipment rack or on a flat surface.
The site should meet the following requirements:
Installation and safety considerations
22
Brocade ICX 6650 Hardware Installation Guide
53-1003083-01