Displaying syslog messages for temperature, Changing the temperature warning level – Brocade ICX 6650 Hardware Installation Guide User Manual
Page 60

Current temperature : 41.5 deg-C
MAC-Left Temperature Readings:
Current temperature : 42.0 deg-C
MAC-Right Temperature Readings:
Current temperature : 42.5 deg-C
MAC-Front Temperature Readings:
Current temperature : 44.5 deg-C
CPU Temperature Readings:
Current temperature : 41.0 deg-C
Center Temperature Readings:
Current temperature : 26.0 deg-C
sensor A Temperature Readings:
Current temperature : 34.5 deg-C
sensor B Temperature Readings:
Current temperature : 35.5 deg-C
sensor C Temperature Readings:
Current temperature : 47.5 deg-C
sensor D Temperature Readings:
Current temperature : 39.5 deg-C
Warning level.......: 68.0 deg-C
Shutdown level......: 85.0 deg-C
Boot Prom MAC : 00.00.00
Management MAC: 00-00-00
Syntax: show chassis
Displaying syslog messages for temperature
The software sends a syslog message and an SNMP trap if the temperature crosses the warning or
shutdown thresholds. The following method describes how to view the system log on the device. If you
have configured the device to use a syslog server or SNMP trap receiver, refer to the documentation
for the server or receiver.
To display the system log, enter the show log command at any CLI level.
device# show log
Syslog logging: enabled (0 messages dropped, 0 flushes, 0 overruns)
Buffer logging: level ACDMEINW, 8 messages logged
level code: A=alert C=critical D=debugging M=emergency E=error
I=informational N=notification W=warning
Static Log Buffer:
Dynamic Log Buffer (50 entries):
at 0 days 0 hours 2 minutes 0 seconds, level alert
Temperature 48.0 C degrees, warning level 45.0 C degrees, shutdown level 55.0 C
degrees
at 0 days 0 hours 1 minutes 0 seconds, level alert
Temperature 40.0 C degrees, warning level 35.0 C degrees, shutdown level 45.0 C
degrees
Changing the temperature warning level
To change the temperature at which the device sends a syslog message and an SNMP trap, enter a
command similar to the following at the Privileged EXEC level of the CLI.
device# temperature warn 85
Syntax: temperature warn value
The value variable is the temperature warning level, in Celsius. You cannot set this level higher than
the temperature shutdown level, which is automatically set by the device.
If you change the device hardware configuration (for example, by adding a fan tray), the device may
change the temperature shutdown level the next time it boots. This can result in the temperature
warning level being higher than the temperature shutdown level. If this happens, a warning message is
displayed during bootup.
Displaying syslog messages for temperature
58
Brocade ICX 6650 Hardware Installation Guide
53-1003083-01