#7 Program control related (only when program control is ON)
<#1 Program parameter setting>
Parameter
Selectable Range or Selections
Initial Value
#1 Pattern initial setting
Program initial setting > Pattern number
1 to 4 (/PG1), 1 to 30 (/PG2)
1
Program initial setting > Segments
0 to 99
0
Program initial setting > Segment setting method
Time, Ramp
Time
Program initial setting > Pattern name
Up to 16 alphanumeric characters
Pattern 1
Program initial setting > Action loop > Loop 1 to 6
On/Off
Off
#2 Wait action setting
Wait action setting > Wait zone 1 to 5 >
Loop 1 to 6
On/Off
Off
> High, Low
EUS (100.0%) of the measurement span
1 digit
Wait action setting > Wait time
00:00:00 to 99:59:59
00:00:00
#3 Pattern start setting
Pattern start setting > Start target setpoint >
Loop 1 to 6
EU (0% to 100%) of the measurement span
–200.0
Pattern start setting > Start code
StartTargetSP, RampPV1 to RampPV6, TimePV,
StartTargetSP
#4 Program pattern setting
Program pattern setting > Segment number
1 to specified number of segments
1
Program pattern setting > Ramp/Soak select
Ramp, Soak
Ramp
Program pattern setting > Target setpoint >
Loop 1 to 6
EU (0% to 100%) of the measurement span
–200.0
Program pattern setting > Segment time
1
00:00:00 to 99:59:59
00:00:01
Program pattern setting > Ramp-rate time unit
2
Hour, Minute
Hour
Program pattern setting > Ramp
2
1 digit to EUS (100.0%) of the measurement span
1 digit
Program pattern setting > Segment PID group No. 1 to specified PID number
1
Program pattern setting > Segment shift action
Continue, HoldShift, LocalShift, ResetShift
Continue
Program pattern setting > Wait action
Off, Shift, Within
Off
Program pattern setting > Wait zone number
1 to 5
1
#5 Event setting
Event setting > Segment number
1 to specified number of segments
1
Event setting > Event kind
PVEvent, TimeEvent
TimeEvent
Event setting > TimeEvent 1 to 16
On1, On2, On3, Off
Off
Event setting > TimeEvent 1 to 16 >
On-time, Off-time
00:00:00 to 99:59:59
00:00:00
Event setting > PVEvent 1 to 16 > Loop
Off, 1 to 6
Off
Event setting > PVEvent 1 to 16 > Loop > Type
PV-High, PV-Low, Deviation-High, Deviation-Low, Deviation-H&L,
PV-High
Dev-within-H6L, SP-High, SP-Low, Output-High, Output-Low
Event setting > PVEvent 1 to 16 > Loop > Value
PV: EU (0% to 100%) of the measurement span
1370.0
Deviation: EUS (0% to 100%)
of the measurement span
1570.0
SP: EU (0% to 100%) of the measurement span
1370.0
Output: −5.0 % to 105.0 %
105.0 %
#6 Hysteresis (PV event)
Hysteresis (PV event) > PV event >
Hysteresis 1 to 16
0.0% to 10.0
0.5%
#7 Repeat action setting
Repeat action setting > Repeat action
Off, On, Repeat
Off
Repeat action setting > On > Repeat frequency
1 to 999
1
Repeat action setting > Repeat action
1 to specified number of segments
1
> Repeat start segment
Repeat action setting > Repeat action
1 to specified number of segments
1
> Repeat end segment
1
When [Time] is specified for the segment setting method.
2
When [Ramp] is specified for the segment setting method.
<#2 Event output setting*>
Parameter
Selectable Range or Selections
Initial Value
Event output > Pattern number
1 to 4 (/PG1), 1 to 30 (/PG2)
1
Event output > Event kind
PVEvent, TimeEvent
TimeEvent
Event output > Relay Output EV1 to 16
On, Off
Off
Event output > On EV1 to 16 > Number
DO001 to DO006, DO101 to DO106, DO201 to DO206,
DO001
RO001 to RO012, SW001 to SW036
Program pattern end signal > Relay Output
On, Off
Off
Program pattern end signal > On > Number
DO001 to DO006, DO101 to DO106, DO201 to DO206,
DO001
RO001 to RO012, SW001 to SW036
* With version 3.01, event output setting is included as item #6 within #1 Program pattern setting.
List of Parameters