7 communication <#1 ethernet, serial, 2 ftp client, 3 control (login, timeout) – Yokogawa Data Acquisition with PID Control CX2000 User Manual
Page 46: 4 modbus master
![background image](/manuals/360259/46/background.png)
46
IM 04L31A01-02E
#7 Communication
<#1 Ethernet, Serial>
Parameter
Selectable Range or Selections
Initial Value
Ethernet > IP-address
–
0.0.0.0
Ethernet > Subnet mask
–
0.0.0.0
Ethernet > Default gateway
–
0.0.0.0
Ethernet > DNS On/Off
On/Off
Off
Ethernet > Server search order > Primary
–
0.0.0.0
Ethernet > Server search order > Secondary
–
0.0.0.0
Ethernet > Host name
Up to 64 alphanumeric characters
–
Ethernet > Domain name
Up to 64 alphanumeric characters
–
Ethernet > Domain suffix search order > Primary
Up to 64 alphanumeric characters
–
Ethernet > Domain suffix search order > Secondary Up to 64 alphanumeric characters
–
Serial > Baud rate
1200, 2400, 4800, 9600, 19200, or 38400 bps
9600 bps
Serial > Data length
7 or 8
8 bit
Serial > Parity
Odd, Even, and None
Even
Serial > RS-232 > Handshaking
Off:Off, XON:XON, XON:RS, or CS:RS
Off:Off
Serial > RS-422/485 > Address
1 to 32
1
Serial > RS-422/485 > Protocol
Normal, Modbus, Modbus-M, or Ladder*
Normal
Memory output
Ethernet or serial
Ethernet
*
Ladder is only on models with the ladder communication option
<#2 FTP client>
Parameter
Selectable Range or Selections
Initial Value
FTP transfer file > Disp&Event data
On/Off
Off
FTP transfer file > Report
On/Off
Off
FTP connection
Primary or Secondary
Primary
FTP connection > FTP server name
Up to 64 alphanumeric characters
–
FTP connection > Port number
1 to 65535
21
FTP connection > Login name
Up to 32 alphanumeric characters
–
FTP connection > Password
Up to 32 alphanumeric characters
–
FTP connection > Account
Up to 32 alphanumeric characters
–
FTP connection > PASV mode
On/Off
Off
FTP connection > Initial path
Up to 64 alphanumeric characters
–
<#3 Control (Login, Timeout)>
Parameter
Selectable Range or Selections
Initial Value
Ethernet login > Use/Not
Use/Not
Not
Ethernet login > Level
admin, user1, user2, user3, user4, user5,
admin
or user6
Ethernet login > Level > On/Off
On/Off
On
Ethernet login > Level > User name
Up to 16 alphanumeric characters
admin
Ethernet login > Level > Password
Up to 6 alphanumeric characters
0
Application time out > On/Off
On/Off
Off
Application time out > Time
1 to 120
1 min
Keep alive > On/Off
On/Off
On
<#4 Modbus master>
Parameter
Selectable Range or Selections
Initial Value
Basic settings > Read cycle
125 ms, 250 ms, 500 ms, 1 s, 2 s, 5 s, 10 s, 15 s,
2 s
20s, or 30s
Basic settings > Timeout
125 ms, 250 ms, 500 ms, 1 s, 2 s, 5 s, 10 s, or 1 min 2 s
Basic settings > Retrials
Off, 1, 2, 3, 4, 5, 10, or 20
1
Command settings > 1 to 8
On/Off
Off
Command settings > 1 to 8 > Comm. Data First
C01 to C30
C01
Command settings > 1 to 8 > Comm. Data Last
C01 to C30
C01
Command settings > 1 to 8 > Address
1 to 247
1
Command settings > 1 to 8 > Salve Registers
Input registers: 30001 to 39999, 300001 to 365535
30001
Hold registers: 40001 to 49999, 400001 to 465535
Command settings > 1 to 8 > Type
INT16, UINT16, INT32_B, INT32_L, UINT32_B,
INT16
UINT32_L, FLOAT_B, or FLOAT_L
List of Parameters