Parameter

Selectable Range or Selections

Initial Value

AUX > Loop number

1 to 6

1

AUX > Remote setting

Off or Remote

Off

AUX > Alarm mode

ALWAYS, STOP, or STOP/MAN

ALWAYS

AUX > SP No. selection source 1 to 6

On/Off

1: On, 2-6: Off

AUX > PV/SP math

On/Off

Off

AUX > CLOG error

Error, Skip

Error

AUX > Event output setting

Common/Separate

Common

<#3 Output processing>

Parameter

Selectable Range or Selections

Initial Value

Output processing > Loop number

1 to 6

1

Output processing > Control output

Relay, Voltage-pulse, Current-output,

Current-output

or On/Off-control

Output processing > Cycle time

1 s to 1000 s

30 s

Output processing > Analog-output type

4-20 mA, 0-20 mA, 20-4 mA, or 20-0 mA

4-20 mA

<#4 Relay>

Parameter

Selectable Range or Selections

Initial Value

Relay > Module

CTRL1-2, CTRL3-4, CTRL5-6, or EXTDIO

CTRL1-2

Relay > FAIL

On/Off

Off

Relay > Self diagnosis

On/Off

Off

Relay > DO001 to 006

De_energize/Hold, De_energize/Nonhold,

Energize/Nonhold

Energize/Hold, or Energize/Nonhold

Relay > RO001 to 012

De_energize/hold, De_energize/Nonhold,

Energize/Nonhold

Energize/Hold, or Energize/Nonhold

<#5 Tuning setting>

Parameter

Selectable Range or Selections

Initial Value

Tuning setting > Loop number

1 to 6

1

Tuning setting > 01 to 21

On/Off

01-12: On, 13-21: Off

Tuning setting > 01 to 21 > Item ID

SP, A1, A2, A3, A4, P,I, D, OH, OL, MR,

01: SP, 02: A1, 03: A2,

PO, H, DR, BS1, FL1, BS2, FL2, RT, RBS,

04: A3, 05: A4, 06: P,

RFL, or W01 to W36

07: I, 08: D, 09: OH,
10: OL, 11: MR,
12: PO, 13 - 21: SP

Tuning setting > 01 to 21 > Item name

Up to 6 alphanumeric characters

01-12: same as Item ID,
13 - 21: –

<#6 External loop setting>

Parameter

Value or Selections

Initial Value

#1 Basic setting
Loop number

Ext1 to Ext16

Ext1

Comm. Off/On

On/Off

Off

Modbus address

1 to 247

1

Connecting model

UT320, UT321, UT350, UT351, UT420, UT450, UT520, UT550,

UT320

UT750, or Others

Loop select

First or Second

First

Tag

Up to 8 alphanumeric characters

EXT-01

Tag comment

Up to 8 alphanumeric characters

Auto reading

Execute

Execute

PV > Decimals

0 to 4

0

PV > Unit

Up to 6 alphanumeric characters

SP > Decimals

0 to 4

0

SP > Unit

Up to 6 alphanumeric characters

OUT > Decimals

0 to 4

0

OUT > Unit

Up to 6 alphanumeric characters

%

Control span lower

–30000 to 30000, span width: 30000

0

Control span upper

–30000 to 30000, span width: 30000

10