Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 12

background image

12

IM 04L31A01-02E

2.

Press the

#1 soft key

(Control action, Input setting).

3.

Press the

arrow keys

to move the cursor (blue) to the setup item box, press the

soft

key

of each value according to the following figure, and then press the

DISP/ENTER

key

.

Select 1

Select Single
(single loop)

Select Temp
(Set initial PID to P = 5%,
I = 240 s, and D = 60 s)

4.

Press the

ESC key

to return to the basic control setting menu.

5.

Press the

#3 soft key

(Output processing).

6.

Press the

arrow keys

to move the cursor (blue) to the setup item box, press the

soft

key

of each value according to the following figure, and then press the

DISP/ENTER

key

.

To set Cycle time, press the

Input soft key

to open a numeric entry pop-up window

as shown in the figure below. Enter the value using the

Character/Number key

and

the

Space soft key

and then press the

DISP/ENTER key

.

Select 1

Set to 3 s

Select Voltage-pulse

* No need to set
Analog-output type

Numeric entry pop-up
window

7.

Press the

ESC key

twice to return to the menu display (basic setting mode 2/2).

8.

Press the

End soft key

.

A confirmation window shown below opens.

9.

Press the

DISP/ENTER key

to confirm the settings.

Examples of Control Setup Operation