6 report e-mail settings, 9 aux, time zone, 10 control <#1 control action, input setting – Yokogawa Data Acquisition with PID Control CX2000 User Manual
Page 48: 2 di/do/sw-registration/aux (alarm mode...)

48
IM 04L31A01-02E
<#6 Report E-Mail Settings>
Parameter
Selectable Range or Selections
Initial Value
Report E-Mail settings > Recipient1
On/Off
Off
Report E-Mail settings > Recipient2
On/Off
Off
Report E-Mail settings > Include source URL
On/Off
Off
Report E-Mail settings > Subject
Up to 32 alphanumeric characters
(CX) Report_data
Report E-Mail settings > Header1
Up to 64 alphanumeric characters
–
Report E-Mail settings > Header2
Up to 64 alphanumeric characters
–
#9 Aux, Time zone
Parameter
Selectable Range or Selections
Initial Value
AUX > Tag/Channel
Tag/Channel
Tag
AUX > Memory alarm
Off, 1 h, 2 h, 5 h, 10 h, 20 h, 50 h, or 100 h
1 h
AUX > Language
English, Japanese, German, French, or Chinese
English
AUX > Partial
Use/Not
Not
Time zone > Difference from GMT
–1200 to 1200
0
Batch
Use/Not
Use
#10 Control
<#1 Control action, Input setting>
Parameter
Selectable Range or Selections
Initial Value
Control action > PID number
1 to 8
8
Control action > Control period
250 ms, 500 ms, or 1 s
*
250 ms
Control action > Zone PID
On/Off
Off
Control action > Restart mode
Continue, Manual, or Auto
Continue
Control action > Restart mode (Program)
Continue, Manual, or Reset
Continue
Control action > Initial PID
Temp or Press+Flow
Temp
Control action > 6/4loop select
6 loop or 4 loop
6 loop
Control action > Auto tuning
On/Off
Off
Control action > Loop number
1 to 6
1
Control action > Control mode
Off, Single, Cascade, PVSwitching, or Retrans
Single
Control action > Control mode > Method
Range, PVHigh, or Signal
Range
Control action > Program control
On/Off
Off
Control action > PID control mode
Follow-up or Fixed-point
Follow-up
Input setting > Loop number
1 to 6
1
Input setting > Burnout > Measure1
Off, Up, or Down
Up
Input setting > Burnout > Measure2
Off, Up, or Down
Up
Input setting > Burnout > Remote
Off, Up, or Down
Up
Input setting > RJC > Measure1
External, Internal
Internal
Input setting > RJC > Measure1 > Volt (uV)
–20000 µV to 20000 µV
0 µV
Input setting > RJC > Measure2
External, Internal
Internal
Input setting > RJC > Measure2 > Volt (uV)
–20000 µV to 20000 µV
0 µV
Input setting > RJC > Remote
External, Internal
Internal
Input setting > RJC > Remote > Volt (uV)
–20000 µV to 20000 µV
0 µV
*
Fixed to 1 s for A/D integral time of 100 ms.
<#2 DI/DO/SW-registration/AUX (Alarm mode...)>
Parameter
Selectable Range or Selections
Initial Value
Contact input > Module
CTRL1-DI, CTRL2-DI, CTRL3-DI, EXT1-RI,
CTRL1-DI
CTRL1-DO, CTRL2-DO, CTRL3-DO, EXT1-RO,
INT-SW1, INT-SW2, INT-SW3
Contact input > DI001 to 006
None, AllControlStop,
None
Contact input > DI101 to 106
AllControlStart, ControlStart/Stop (1 to 6),
Remote/Local (1 to 6), Auto/Man (1 to 6),
Contact input > RI001 to 012
Cascade (1-2 or 3-4), Auto1-2 or 3-4,
Contact input > DO001 to 006
Man1-2 or 3-4, SPNumber0 to 3 bit, ProgramRun,
Contact input > DO101 to 106
ProgramReset, Hold, Advance, PatternNo0 to 4bit,
Contact input > DO201 to 206
PVSwitching1 to 4, MemoryStart/Stop,
Contact input > RO001 to 012
Trigger, AlarmAck, TimeAdjust,
Contact input > SW001 to 036
MathStart/Stop, MathReset, ManualSample,
Panel1Load to Panel3Load, Message1 to 8,
Snapshot
List of Parameters