Yokogawa Data Acquisition with PID Control CX2000 User Manual
Page 22

22
IM 04L31A01-02E
3.
Press the
arrow keys
to move the cursor (blue) to the Input type box, press the
PV1
soft key
, and set other parameters as shown in the figure below.
Check that 1 is
selected
Select 1-5V
Select PV1
Set to 0.00
Set to 300.00
Set to kg/h
4.
Press the
DISP/ENTER key
.
A confirmation window opens.
5.
Press the
DISP/ENTER key
to confirm the settings.
6.
Press the
arrow keys
to move the cursor (blue) to the Input type box, press the
PV2
soft key
, and set other parameters as shown in the figure below.
Check that 1 is
selected
Select 1-5V
Select PV2
Set to 0.00
Set to 30.00
Set to kg/h
7.
Press the
DISP/ENTER key
.
A confirmation window opens.
8.
Press the
DISP/ENTER key
to confirm the settings.
9.
Press the
arrow keys
to move the cursor (blue) to the Input type box, press the
PVrange soft key
, and set other parameters as shown in the figure below.
Set to 0.00
Set to 300.00
Set to kg/h
Check that 1 is
selected
Select PVrange
10.
Press the
DISP/ENTER key
.
A confirmation window opens.
11.
Press the
DISP/ENTER key
to confirm the settings.
Examples of Control Setup Operation