Yokogawa Data Acquisition with PID Control CX2000 User Manual
Page 21

21
IM 04L31A01-02E
2.
Press the
#1 soft key
(Control action, Input setting).
3.
Press the
arrow keys
to move the cursor (blue) to the setup item box, press the
soft
key
of each value according to the following figure, and press the
DISP/ENTER key
.
Select 1
Select PVSwitching
Select Press+Flow
Select Signal
4.
Press the
ESC key
to return to the basic control setting menu.
5.
Press the
#3 soft key
(Output processing).
6.
Press the
arrow keys
to move the cursor (blue) to the setup item box, press the
soft key
of
each value according to the following figure, and press the
DISP/ENTER key
.
Select 1
Select 4-20mA
Select Current-output
* No need to set
Cycle time
7.
Press the
ESC key
twice to return to the menu display (basic setting mode 2/2).
8.
Press the
End soft key
.
A confirmation window shown below opens.
9.
Press the
DISP/ENTER key
to confirm the settings.
Setting the Control Input Range in Setting Mode
1.
From the operation display, click the
MENU key
to display the control setting menu
shown below.
2.
Press the
#1 soft key
(Control input range).
Examples of Control Setup Operation