beautypg.com

Watlow Series SD31 PID with Optional Countdown Timer User Manual

Page 34

background image

Wa t l o w S e r i e s S D 3 1

32

C h a p t e r 6 O p e r a t i o n s

Display

Parameter Name

Description

Settings

Range

(Integer values for Modbus

in parentheses.)

Default

Modbus*

(less 40,001

offset)

Read/Write

Appears if:

Note: Parameters appear on the Operations Page only if activated from the Programming Page. See page 16 for Operations Page defaults.

Note: Some values will be rounded off to fit in the four-character display. Full values can be read with Modbus.

* Low register numbers contain the two higher bytes; high register numbers contain the two lower bytes of the four-byte integer.
Decimal precision is implied at three decimal places unless otherwise noted.

Caution: Writing to registers continuously, such as ramping set points via comms, will damage the SD31 EEPROM memory. See page 59.

[A1;hi]

[A1.hi]

Alarm 1 High

Set the high alarm set point.

Deviation: 0 to 9999
(0000 to 9999000)

Process: range of sensor, if
[`SEN] is set to [``tc] or
[`rtd]

-1999 to 9999 if

[`SEN] is

set to

[`Ma] or [uolt].

(-1999000 to 9999000)

999 (dev)

1500 (pro)

*100, 101
R/W

(dev)

*104, 105
R/W

(pro)

[Ot`1] is set to
[dE;AL] or [Pr;AL].

[A1;Lo]

[A1.Lo]

Alarm 1 Low

Set the low alarm set point.

Deviation: -1999 to 0
(-1999000 to 0000)

Process: range of sensor, if
[`SEN] is set to [``tc] or
[`rtd]

-1999 to 9999 if

[`SEN] is

set to

[`Ma] or [uolt].

(-1999000 to 9999000)

-999 (dev)

32 (pro)

*98, 99
R/W

(dev)

*102, 103
R/W

(pro)

[Ot`1] is set to
[dE;AL] or [Pr;AL]

[A2;hi]

[A2.hi]

Alarm 2 High

Set the high alarm set point.

Deviation: 0 to 9999

Process: range of sensor, if
[`SEN] is set to [``tc] or
[`rtd]

-1999 to 9999 if

[`SEN] is

set to

[`Ma] or [uolt].

999 (dev)

1500 (pro)

[Ot`2] is set to
[dE;AL] or [Pr;AL].

[A2;Lo]

[A2.Lo]

Alarm 2 Low

Set the low alarm set point.

Deviation: -1999 to 0

Process: range of sensor, if
[`SEN] is set to [``tc] or
[`rtd]

-1999 to 9999 if

[`SEN] is

set to

[`Ma] or [uolt].

-999 (dev)

32 (pro)

[Ot`2] is set to
[dE;AL] or [Pr;AL].

[hour]

[hour]

Countdown Time - Hours

Displays the number of hours remaining
for the countdown time.

0 to 99
hours
(0 to 99000)

0

375 R

Timer model only,
SD31-XXXX-XTXX.
[`Ot1] or [`Ot2]is set
to

[tim].

[Min]

[Min]

Countdown Time - Minutes

Set the number of minutes remaining for
the countdown time.

0 to 59
minutes
(0 to 59000)

0

376 R

Timer model only,
SD31-XXXX-XTXX.
[`Ot1] or [`Ot2]is set
to

[tim].