Wa t l o w S e r i e s S D 3 1

29

C h a p t e r 6 O p e r a t i o n s

Note: Parameters appear on the Operations Page only if activated from the Programming Page. See page 16 for Operations Page defaults.

Note: Some values will be rounded off to fit in the four-character display. Full values can be read with Modbus.

* Low register numbers contain the two higher bytes; high register numbers contain the two lower bytes of the four-byte integer.
Decimal precision is implied at three decimal places unless otherwise noted.

Caution: Writing to registers continuously, such as ramping set points via comms, will damage the SD31 EEPROM memory. See page 59.

Display

Parameter Name

Description

Settings

Range

(Integer values for Modbus

in parentheses.)

Default

Modbus*

(less 40,001

offset)

Read/Write

Appears if:

Operations Parameters Table

6

These parameters can be selected to appear on the Operations Page. Select parameters to appear on the Operations
Page on the Programming Page.

To go to the Operations Page, press and hold the Infinity Key

ˆ for three seconds from the Home Page.

[Oper] will appear in the display.

Press the Down

¯ or Up ¿ keys to move through the Operations Page parameters.

To view or change a parameter value, press and hold the

ß Key.

Press the Down

¯ or Up ¿ keys to change the parameter value.

Press the Infinity Key

ˆ at any time to return to the Home Page.

[Po;ht]
[Po.ht]

Power Heat

Displays the current heat control power.

0.0 to 100.0% power
(000 to 10000)
(Two decimal places implied
for Modbus.)

NA

256 R

[A-M] is set to [auto]
and at least one output
is set to

[hEAt].

[Po;CL]
[Po.CL]

Power Cool

Displays the current cool control power.

0.0 to 100.0% power
(000 to 10000)
(Two decimal places implied
for Modbus.)

NA

257 R

[A-M] is set to [auto]
and at least one output
is set to

[Cool].

[A-m]
[A-M]

Auto-Manual Mode

Set the control mode.

[auto] auto mode (0)
[Man] manual mode (1)

[auto] (0)

25 R/W

Always appears.

[`Aut]
[ Aut]

Autotune

Start an autotune.

[`OFF] off (0)
[``On] on (1)

[`OFF] (0)

215 R/W

At least one output is
set to

[hEAt] or

[Cool].

[`Cal]

[ CAL]

Calibration Offset

Offset the input reading.

-999 to 999
(-999000 to 999000)

0.0

*85, 86
R/W

Always appears.

[ht;m]

[ht.M]

Heat Control Method

Set the heat control method.

[`OFF] off (0)
[`PID] PID (1)
[on;of] on-off (2)

[`PID] (1)

213 R/W

At least one output is
set to

[hEAt].

[Pb;ht]

[Pb.ht]

Proportional Band Heat

Set the proportional band for the heat
outputs.

1 to 999°F, if

[`Sen] is set to

[``tc] or [`rtd]
(1000 to 999000)

0.000 to 999 units, if

[`Sen]

is set to

[`mA] or [uolt].

(0000 to 999000)

25

25

*216, 217
R/W

*220, 221
R/W

At least one output is
set to

[hEAt] and

[ht;m] is set to
[`PId].

[rE;ht]
[rE.ht]

Reset Heat

Set the PID reset in repeats per minute
for the heat outputs.

0.00 to 99.99 repeats per
minute
(0000 to 99990)

0.00: disabled

0.00

*224, 225
R/W
(Modbus
value is in-
tegral,
which is
the inverse
of reset.)

At least one output is
set to

[hEAt], [ht;m]

is set to

[`PId], and

[Unit] is set to [``US].

[It;ht]

[It.ht]

Integral Heat

Set the PID integral in minutes per re-
peat for the heat outputs.

0.00 to 99.99 minutes/per
repeat
(0000 to 99990)

0.00: disabled

0.00

*224, 225
R/W

At least one output is
set to

[hEAt], [ht;m]

is set to

[`PId], and

[Unit] is set to [``SI].