Wa t l o w S e r i e s S D 3 1
■
28
■
C h a p t e r 5 S e t u p
Display
Parameter Name
Description
Settings
Range
(Integer values for Modbus
in parentheses.)
Default
Modbus*
(less 40,001
offset)
Read/Write
Appears if:
Note: Some values will be rounded off to fit in the four-character display. Full values can be read with Modbus.
* Low register numbers contain the two higher bytes; high register numbers contain the two lower bytes of the four-byte integer.
Decimal precision is implied at three decimal places unless otherwise noted.
Caution: Writing to registers continuously, such as ramping set points via comms, will damage the SD31 EEPROM memory. See page 59.
[``rP]
[ rP]
Ramping Mode
Select when the control set point ramps to
the defined end set point.
[`OFF] off (0)
[`Str] ramps on start-up
only (1)
[``On] ramps at start-up or
any set point change (2)
[`OFF] (0)
266 R/W
Always active.
[rP;Sc]
[rP.Sc]
Ramp Scale
Select the scale of the ramp rate.
[hour] degrees/hour (0)
[Min] degrees/minute (1)
[hour] (0)
267 R/W
[``rP] is set to [`Str]
or
[``On].
[rP;rt]
[rP.rt]
Ramp Rate
Set the rate for the set point ramp.
0 to 9999
(0000 to 9999000)
100
*268, 269
R/W
[``rP] is set to [`Str]
or
[``On].
Does not appear if
[``rP] is set to [`OFF].
[Addr]
[Addr]
Modbus Device Address
Set the device address for communica-
tions. Every controller on a network must
have a unique address.
1 to 247
1
This can
only be set
from the
controller
front panel.
Output 2 is a communi-
cations output.
(SD_ _ - _ _ U _ - _ _ _ _ )
[bAud]
[bAud]
Baud Rate
Set the baud rate at which the communi-
cations occurs.
[9600] 9600 baud
[`19;2] 19,200 baud
[`38;4] 38,400 baud
[9600]
This can
only be set
from the
controller
front panel.
Output 2 is a communi-
cations output.
(SD_ _ - _ _ U _ - _ _ _ _ )
[`LOC]
[ LOC]
Lockout
Set the security level for the user inter-
face.
[```0] (0) No lockout
[```1] (1) Set Point,
Auto/Manual, alarms only
[```2] (2) Set Point,
Auto/Manual, only
[```3] (3) Set Point only
[```4] (4) Full lockout
See the Features Chapter
for details.
[```0] (0)
43 R/W
Always active.